Fire Alarm Computer 8000C / M
Trouble
code no.
Possible cause 1st measure 2nd measure
037
038
esserbus
transponder has
identified fault with its
external voltage
Check whether the externa
l
switching voltage of the
esserbus
transponder is i
n
the correct voltage range.
None
039
Communication between
esserbus
transponder und
panel disturbed for 100
seconds.
Notify ESSER Customer
Service.
None
043
Communication between
esserbus
®
communication
transponder for the 8010
fire and extinguishing pane
l
and the 8010 fire and
extinguishing panel has
been malfunctioning for
over 100 sec.
Check correct functioning
of the 8010 fire and
extinguishing panel.
Correct any malfunctions o
f
the fire and extinguishing
panel and switch on the
esserbus
®
-communication
transponder via the FACP
keyboard
Notify ESSER Customer
Service.
044
Communication between
FACP and esserbus
®
communication
transponder for the 8010
fire and extinguishing pane
l
has been malfunctioning
for over 100 sec.
Notify ESSER Customer
Service.
None
048 see 001 --- ---
052
053
see 020 --- ---
060 see 028 --- ---
066
Loop wiring has been
changed.
Connect service PC and
perform configuration
check.
Match customer data
programming
067
Detector cannot be
addressed with serial
number. The detector
changed at this location is
faulty or absent.
Check location to see
whether detector is absent
or improperly installed in
detector base. Switch on
loop, perform test on
detector zone.
Change detector. Activate
Detector change
function in
panel.
068
The detector that was
positioned at this location
has been installed at a
different location. One or
more detectors on the loop
have been interchanged.
If this change is desired,
you must activate the
Detector change
function at
the panel.
If this change is not
desired, connect service
PC and run a configuration
check. Re-program
customer data.
M
eaning of the three-digit trouble code

Table of Contents