P74
x/EN AP/Na7
Application Notes
(AP) 6
-46 MiCOM P74
1, P742, P743
AP
Compensated:
Minimum two phase busbar fault current
Maximum single-phase steady state busbar fault current
Maximum load current on the biggest feeder
Optional: Maximum three phase busbar fault current
With impedance:
Minimum two phase busbar fault current
Minimum single phase to earth busbar fault current
Minimum load current on the smallest feeder
Maximum load current on the biggest feeder
Optional: Maximum three phase busbar fault current
Maximum substation short-circuit withstand time
7.4 Switchgear
Nominal CT ratio
Highest nominal primary current (CT In Max)
Lowest nominal primary current (CT In Min)
CT Knee point voltage (Vk) for each CT
CT secondary resistance (RCT) for each CT
Length and cross section of the conductors between each CT and the peripheral unit.
(In the absence of precise information, an estimate taken from the lowest CT ratio will
suffice)
Auxiliary contacts of disconnecting switches and tripping orders for circuit breaker failure
(irrespective of the how the CB fail scheme is to be implemented i.e. internally or
externally initiated)
7.5 Cubicle specifications
Cubicle specification is contract specific.
However, GE propose the following:
Single cubicle: 800x800x2000
Double cubicle: 1600x800x2000
Model: Schroff type Proline
Colour: RAL 7032