P74
x/EN TD/Na7
Technical Data
(TD) 2
-12 MiCOM P74
1, P742, P743
TD
Measurements and records List
Fault Recorder
Records for the last 5 faults
Central Unit:
Active Setting group
Faulty phase
Protection started/operated (87BB, 50BF,
Dead Zone…)
Fault occurrence time and duration
Check Zone values (Diff. & Bias for A, B, C,
N)
Faulty zone(s)
Topology prior the fault occurrence
Peripheral Unit:
Active setting group
Indication of the tripped phases
Protection started/operated (87BB, 50BF,
Dead Zone…)
Relay Trip Time and duration
Relay Trip Time
Faulty phase currents (A, B, C, N)
Event Recorder
Records for the last 512 events
Oscillography
(Disturbance Recorder)
Central Unit:
Duration: Fixed value 1.2 s
Trigger Position: 0…100% (step 33.3%)
Analogue Channel 1: (up to 8)
Digital Input 1: (up to 32)
Peripheral Unit:
Duration: Settable from 1.2 to 10.5s
Trigger Position: 0…100% (step 0.1%)
Trigger Mode: Single / Extended
Analogue Channel 1: (up to 4):
Digital Input 1: (up to 32):
Selected binary channel assignment from
any DDB status point within the relay (opto
input, output contact, alarms, starts, trips,
controls, logic…).
Sampling frequency: 600Hz
Communications
RP1 Protocol: Courier
RP1 Address (courier): 6…34
Inactivity Timer: 1…30 minutes
RP1 Port Config (Courier):
K Bus / EIA485 (RS485)
RP1 Comms Mode (EIA485 (RS485)):
IEC60870 FT1.2 Frame
10-Bit NoParity
RP1 Baud Rate (EIA485 (RS485)):
9600 / 19200 / 38400 bits/s
RP1 Read Only: Disabled/Enabled
Optional Second Rear
Communication
RP2 Protocol: Courier (fixed)
RP2 Port Config:
Courier over EIA(RS)232
Courier over EIA(RS)485
K-Bus
RP2 Comms. Mode:
IEC60870 FT1.2 Frame
10-Bit NoParity
RP2 Address: 0…255
RP2 InactivTimer: 1…30mins
RP2 Baud Rate:
9600 / 19200 / 38400 bits/s
RP2 Read Only: Disabled/Enabled
Optional Ethernet Port
NIC Tunl Timeout: 1…30mins
NIC Link Report: Alarm / Event / None
NIC Link Timeout: 0.1…60s
NIC Read Only: Disabled/Enabled