EasyManua.ls Logo

GE P742

GE P742
560 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A
pplication Notes
P74x/EN AP/N
a7
MiCOM P74
1, P742, P743 (AP) 6-
51
AP
The above example shows a double busbar with a bus coupler. It is split into two zones.
There are n feeders connected to the busbar. The bus coupler circuit breaker can have
either a single CT (solution 1) on one side or CTs on both sides (solution 2).
This configuration requires 1 central unit and n + 1 peripheral units for solution 1 or n + 2
peripheral units for solution 2. (The additional peripheral units being for the bus coupler
CTs). The type of peripheral unit used for each bay will depend on the i/o requirements of
the bay in question.
P3786ENa
FIGURE 33: TRADITIONAL DOUBLE BUSBAR APPLICATION
WITH BUS COUPLER AND BUS SECTION
The above example shows a double busbar with both a bus section and a bus coupler. It is
split into four zones. There are n feeders connected to the busbar. The bus coupler and bus
section circuit breakers can have either a single CT (solution 1 and 2) on one side or CTs on
both sides (solution 1a or 2a). This configuration requires 1 central unit and n plus the
following number of peripheral units. The total number of peripheral units required allows for
a peripheral unit for the bus section isolator on the upper bar.
Solution Solution A
1 CT on BC
& 1 CT on BS
Solution B
2 CT on BC
& 2 CT on BS
Solution C
1 CT on BC
& 2 CT on BS
Solution D
2 CT on BC
& 1 CT on BS
Solution 1
Solution 1a
Solution 2
Solution 2a
Number of
peripheral units
required
n + 2 n + 4 n + 3 n + 3
If a second bus coupler is added i.e. one bus coupler either side of the bus section
Using solution 1
for the 2
nd
coupler

Table of Contents

Related product manuals