EasyManua.ls Logo

GE P742

GE P742
560 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
P74x/EN CM/Na7
MiCOM P741, P742, P743
(CM) 10-5
CM
3. EQUIPMENT REQUIRED FOR COMMISSIONING
3.1 Minimum equipment required
Overcurrent test set with interval timer
Multimeter with suitable ac current range, and ac and dc voltage ranges of
0 440V and 0 250V respectively
Continuity tester (if not included in the multimeter)
Optical power meter with sensitivity 0 to 50dBm (to measure the optical signal level)
Note: Modern test equipment may contain many of the above features in
one unit.
3.2 Optional equipment
Multi-finger test plug type P992 (if test block type P991 installed) or MMLB (if using MMLG
blocks)
An electronic or brushless insulation tester with a dc output not exceeding 500V (for
insulation resistance testing when required). This equipment will be required only if the
dielectric test has not been done during the manufacturing process.
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
A printer (for printing a setting record from the portable PC).

Table of Contents