P74
x/EN PL/Na7
Programmable Logic
(PL)
7-
26
MiCOM P74
1, P742, P743
PL
Relay
DDB
No.
English Text Type Source Description
P742
261
Dead Zone Fault
PSL Input Signal
Local Protection
Fault in the dead zone
P742
262
Dead Zone
Phase
PSL Input Signal
Local Protection
Fault in the dead zone on a phase
P742
263
Dead Zone Earth
PSL Input Signal
Local Protection
Fault in the dead zone on the neutral
P742
264
Config OK
PSL Input Signal
Relay Integrity
Correct configuration
P742
265
Config Error
PSL Input Signal
Relay Integrity
Configuration error
P742
266
Config Error
PSL Input Signal
Relay Integrity
Configuration error
P742
267
Config. Valid
PSL Input Signal
Scheme Integrity
Valid Setting configuration
P742
268
Topology valid
PSL Input Signal
Scheme Integrity
Valid Topology file
P742
269
Topo/Set valid
PSL Input Signal
Scheme Integrity
Wrong Topology address
P742
270
All Prot Blocked
PSL Input Signal
Commissioning
All the protections (CU & PU) disabled
P742
288
I> Any Trip
PSL Input Signal
Phase Overcurrent
Overcurrent Trip
P742
289
CBAvailabToTrip
PSL Input Signal
Scheme Integrity
Complement of ddb 297
P742
290
BF Trip Request
PSL Input Signal
50BF Protection
External or internal Breaker failure trip order
request (50BF) Logical OR of DDB 122, 172
and 173
P742
294
INP Block
87BB/P
PSL Input Signal
PSL
Logic input to block the 87BB trip when the fault
is detected by the fault element
P742
295
INP Block
87BB/N
PSL Input Signal
PSL
Logic input to block the 87BB trip when the fault
is detected by the earth fault element
P742
296
I> No Trip
PSL Input Signal
Phase Overcurrent
Complement of ddb 288
P742
297
CBNotAvailToTrip
PSL Input Signal
Scheme Integrity
Logical OR of ddb 121 and 270
P742
298
BFTripNoRequest
PSL Input Signal
50BF Protection
Complement of ddb 290
P742
305
Ctrl CB Trip
PSL Input Signal
Manual
Functionality
Manual Trip Order of the Circuit Breaker
P742
306
Ctrl CB Close
PSL Input Signal
Manual
Functionality
Manual closing order of the Circuit Breaker
P742
307
PU Overhaul
mode
PSL Input Signal
Commissioning
PU in overhaul mode
P742
308
50BF Disabled
PSL Input Signal
Commissioning
PU in 50BF blocked mode Alarm
P742
311
50BF Disabled
PSL Output
Signal
Commissioning
To switch the PU in 50BF blocked mode
P742
312
Overhaul Mode
PSL Output
Signal
Commissioning
To switch the PU in overhaul mode
P742
314
I>BB Enabled
PSL Input Signal
Local protection
Overcurrent Local trip confirmation
P742
315
Trip Rel Latched
PSL Input Signal
Local protection
Trip Relays Latched
P742
316
I>2 Block BB ON
PSL Input Signal
87BB protection
Fast external phase fault criterion to block the
connected zone enabled
P742
317
IN>2 Block BB
ON
PSL Input Signal
87BB protection
Fast external neutral fault criterion to block the
connected zone enabled
P742
318
Reset Trip Relay
PSL Input Signal
Commissioning
To reset the Trip relays
P742
319
Topo/Set
Changed
PSL Input Signal
Commissioning
Change on topology or configuration
P742
320
Q1 Closed
PSL Input Signal
PSL
Isolator 1 closed (not (Q1 Aux. (89b) AND Q1
Aux. (89a)))
P742
321
Q1 Status Alarm
PSL Output
Signal
Scheme Integrity
Isolator 1 discrepancy (Q1 Aux. (89b) = Q1
Aux. (89a) for too long
P742
330
Q6 Closed
PSL Input Signal
PSL
Isolator 6 closed (not (Q6 Aux. (89b) AND Q6
Aux. (89a)))
P742
331
Q6 Status Alarm
PSL Output
Signal
Scheme Integrity
Isolator 6 discrepancy (Q6 Aux. (89b) = Q6
Aux. (89a) for too long
P742
332
CB Closed
PSL Input Signal
PSL
Circuit Breaker closed (not (CB Aux. (52b) AND
CB Aux. (52a)))
P742
333
CB Healthy
PSL Input Signal
PSL
Complement of ddb 121
P742
336
Q1 Status Forced
PSL Input Signal
Commissioning
Isolator 1 status position forced open (by
default) or closed
P742
341
Q6 Status Forced
PSL Input Signal
Commissioning
Isolator 6 status position forced open (by
default) or closed
P742
342
CB Status Forced
PSL Input Signal
Commissioning
CB status position forced open (by default) or
closed
P742
343
Forced Mode ON
PSL Input Signal
Commissioning
When the forced positions of the CB and the
Isolators are used (during commissioning test)
P742
344
CB Aux. 52a
PSL Input Signal
CB Monitoring
ddb 123 or Logical OR of ddb 125 and 127 and
129
P742
345
CB Aux. 52b
PSL Input Signal
CB Monitoring
ddb 124 or Logical AND of ddb 126 and 128
and 130