Programmable Logic
P74x/EN PL/N
a7
MiCOM P74
1, P742, P743
(PL) 7-
31
PL
Relay
DDB
No.
English Text Type Source Description
P742
226
I>BB Start C
PSL Input Signal
Phase Overcurrent
Local overcurrent phase C Trip confirmation for
87BB or 50BF (CU) trip order
P742
179
IN>1 Start
PSL Input Signal
Earth Fault
1st Stage Earth Fault Start
P742
189
IN>1 Timer Block
PSL Input Signal
PSL
Blocking of the 2
nd
stage earth fault time delay
P742
181
IN>1 Trip
PSL Input Signal
Earth Fault
1st Stage Earth Fault Trip
P742
317
IN>2 Block BB
ON
PSL Input Signal
87BB protection
Fast external neutral fault criterion to block the
connected zone enabled
P742
185
IN>2 Start
PSL Input Signal
Earth Fault
2nd Stage Earth Fault Start
P742
191
IN>2 Timer Block
PSL Input Signal
PSL
Blocking of the 2
nd
stage earth fault time delay
P742
187
IN>2 Trip
PSL Input Signal
Earth Fault
2nd Stage Earth Fault Trip
P742
231
IN>BB Block
PSL Input Signal
Earth Fault
Local overcurrent earth to block the 87BB on
external fault
P742
227
IN>BB Start
PSL Input Signal
Earth Fault
Local overcurrent Trip confirmation for the
neutral
P742
295
INP Block
87BB/N
PSL Input Signal
PSL
Logic input to block the 87BB trip when the fault
is detected by the earth fault element
P742
294
INP Block
87BB/P
PSL Input Signal
PSL
Logic input to block the 87BB trip when the fault
is detected by the fault element
P742
923
Int. Node 1
Can be created automatically by the PSL
P742
1023
Int. Node 101
Can be created automatically by the PSL
P742
171
Int. Retrip 3 ph
PSL Input Signal
50BF Protection
Retrip triphase due to a 87BB trip initiation (at
tBF1)
P742
256
Internal Trip
PSL Input Signal
Local Protection
Triphase Trip (87BB, 50BF(CU), I>, IN> or
manual zone trip (CU)).
Trip command directly applied to relay 1, 2, 3
(without PSL)
P742
96
LED 1
LED
Led Conditioner
Red LED 1
P742
103
LED 8
LED
Led Conditioner
Red LED 8
P742
428
LED Cond IN 1
LED_CON
PSL
Assignment of signal to drive LED 1 Red.
P742
435
LED Cond IN 8
LED_CON
PSL
Assignment of signal to drive LED 8 Red.
P742
353
Man CB Cls Fail
PSL Input Signal
Scheme Integrity
Circuit Breaker Failed to Close
(after a manual/operator close command)
P742
354
Man CB Trip Fail
PSL Input Signal
Scheme Integrity
Circuit Breaker Failed to Trip
(after a manual/operator trip command)
P742
166
Man. Close CB
PSL Output
Signal
PSL
Circuit Breaker closing order (CB Control)
P742
167
Man. Trip CB
PSL Output
Signal
PSL
Circuit Breaker tripping order (CB Control)
P742
120
Man.CB Close
Cmd
PSL Output
Signal
PSL
Manual/operator Circuit Breaker trip command
P742
160
Man.Close Q1
Cmd
PSL Output
Signal
PSL
Manual/operator Isolator 1 (switch) closing
command
P742
165
Man.Close Q6
Cmd
PSL Output
Signal
PSL
Manual/operator Isolator 6 (switch) closing
command
P742
260
Man.Trip zone
PSL Input Signal
Commissioning
Manual Trip Order of a zone, general
information common to all PUs, the PU can be
connected to an healthy zone
P742
236
Max Flux ph A
PSL Input Signal
Saturation
Maximum flux reached in the phase A CT
P742
237
Max Flux ph B
PSL Input Signal
Saturation
Maximum flux reached in the phase B CT
P742
238
Max Flux ph C
PSL Input Signal
Saturation
Maximum flux reached in the phase C CT
P742
239
Offset Chan
ABCN
PSL Input Signal
Saturation
Offset current read by the Analog board Phase
A, B, C or N
P742
64
Opto Label 01
OPTO
Opto Input
Opto Input 1
P742
79
Opto Label 16
OPTO
Opto Input
Opto Input 16
P742
312
Overhaul Mode
PSL Output
Signal
Commissioning
To switch the PU in overhaul mode
P742
240
Predict err ph A
PSL Input Signal
Saturation
Variation error phase A (derived current)
P742
241
Predict err ph B
PSL Input Signal
Saturation
Variation error phase B (derived current)
P742
242
Predict err ph C
PSL Input Signal
Saturation
Variation error phase C (derived current)
P742
255
PU CT Fail IN
PSL Input Signal
Scheme Integrity
Internal PU CT failure
P742
307
PU Overhaul
mode
PSL Input Signal
Commissioning
PU in overhaul mode
P742
144
PU->CU Signal
01
PSL Output
Signal
PSL
Virtual Signal 01 from the PU to the CU via the
fibre optic
P742
159
PU->CU Signal
16
PSL Output
Signal
PSL
Virtual Signal 16 from the PU to the CU via the
fibre optic

Table of Contents