Loading...
P74
x/EN TS/Na7
Troubleshooting
(TS) 12-
18
MiCOM P74
1, P742, P743
TS
Hexa Code
Decimal
code
Problem Verify or modify
2007
Coprocessor to Comm. board 0
communication - no IT
Coprocessor or Comm. board 0 or
Comm. board 0 address
3FC0
no IT Comm. board to Coprocessor
board
Coprocessor or Com or ribbon
cable
4008
Relay 1 board missing
Relay 1 board or Relay 1 board
address
4010
Relay 1 board writing error
Relay 1 board
8008
Opto 1 board missing
Opto 1 board or Opto 1 board
address
8010
Opto 1 board read error
Opto 1 board
Logical OR
See lines included in the logical OR
See lines included
Ex: 3006 = 2006 OR 1006
P742 / P743 - INIT MODE
PU_INIT_MAJOR
2000
System error
Coprocessor firmware
4008
External autotest RAM
Coprocessor
4010
Autotest interruptions
Coprocessor
4018
Comm. board autotest
Coprocessor
8001
Main to Coprocessor
communication
Coprocessor or Main board
8002
Main to Coprocessor
communication
Coprocessor or Main board
8003
Main to Coprocessor
communication
Coprocessor or Main board
8004
Main to Coprocessor
communication
Coprocessor or Main board
8005
Main to Coprocessor
communication
Coprocessor or Main board
8006
Main to Coprocessor
communication
Coprocessor or Main board
8007
Main to Coprocessor
communication - no IT
Coprocessor address or
Coprocessor or Main board
Logical OR
See lines included in the logical OR
See lines included
PU_INIT_PERIPH
0200
Analogue module acquisition
problem
Analogue module
0408
Relay 3 board missing
Relay 3 board or Relay 3 board
address
0410
Relay 3 board writing error
Relay 3 board
0808
Opto 3 board missing
Opto 3 board or Opto 3 board
address
0810
Opto 3 board read error
Opto 3 board
1008
Relay 2 board missing
Relay 2 board or Relay 2 board
address
1010
Relay 2 board writing error
Relay 2 board
2008
Opto 2 board missing
Opto 2 board or Opto 2 board
address
2010
Opto 2 board read error
Opto 2 board
4008
Relay 1 board missing
Relay 1 board or Relay 1 board
address
4010
Relay 1 board writing error
Relay 1 board
8008
Opto 1 board missing
Opto 1 board or Opto 1 board
address
8010
Opto 1 board read error
Opto 1 board

Table of Contents