Firmware and Service Manual P74x/EN VH/Na7
Version History
MiCOM P741, P742, P743
(
VH) 16-
3
Relay type: P740 …
Software
Version
Hardware
Suffix
Original
Date of Issue
Description of Changes
S1
Compatibility
Technical
Documentation
Major Minor
33
C3.9 J or K January 2008
The status of the trip relays 1, 2, 3 is stored in BBRAM even if
the “Trip Latched” function is disabled in the column “CB
Control”
The status of the trip relays 1, 2, 3 latched in the PU will not
open in case of loss of communication with the CU
The CU->PU signals are not received in the PU if there is no
CT in the topology of this PU (PU in charge of an isolator bus
section)
The Control Input values are correct after the reboot of the
protection.
V2.14
Patch 33
P740/EN xx/H65
40
D2.2 J or K July 2007
Addition of the Ethernet/IEC61850-8-1 protocol option
Addition of the Demodulated Irig-B option
V2.14
Patch 40
P740/EN xx/H65
40
D2.3 J or K February 2008
The status of the trip relays 1, 2, 3 is stored in BBRAM even if
the “Trip Latched” function is disabled in the column “CB
Control”
The status of the trip relays 1, 2, 3 latched in the PU will not
open in case of loss of communication with the CU
The CU->PU signals are not received in the PU if there is no
CT in the topology of this PU (PU in charge of an isolator bus
section)
The Control Input values are correct after the reboot of the
protection.
V2.14
Patch 40
P740/EN xx/H65
40
D2.5 J or K October 2008
The behaviour of the “Out of Sevice” Led is different between
P74xxxxxxxxxx0xx and P74xxxxxxxxxx5xx
The Delta I Algorithm has been removed.
V2.14
Patch 40
P740/EN xx/K96