2.14.2 Input/output connection to the S-ART type 90T S102.
S-ART unit with 2 inputs and one relay output.
Technical data.
Loops IN 0/IN 1
.................... .......... ......... ..........
Any voltage free contact, normally closed.
(The inputs can also be a normally open - type)
Terminating resistor
............... .......... ......... ..........
None
Max. length of cable
............... .......... ......... ..........
10m
24VDC current consumption
.......... ......... ..........
Relay in normal: 0 mA
Relay activated: 24V/12 mA
12V/6mA
DC Voltage
........ .................... .......... ......... ..........
10V - 30VDC
17V Line current consump.
.... .......... ......... ..........
2ma
Relay switching voltage
.......... .......... ......... ..........
Max. 125V
Relay switching current
.......... .......... ......... ..........
Max. 1A.
Relay max. power DC/AC
...... .......... ......... ..........
30W / 60VA
Temperature range
................ .......... ......... ..........
-25
0
C - +70
0
C
The 17V Line current consumption is the current taken from the bus L+ and L-.
The relay is always controlled by the output OUT1 on the S-ART.(see Output Definitions menu 85)