IDEC SmartRelay functions
4.4 Special functions list - SF
IDEC SmartRelay Manual
138
4.4.3 On-/off-delay
Short description
The on-/off-delay function sets the output after the set on-delay time has expired, and resets it
upon expiration of the off-delay time.
Parameters T
H
and T
L
Note the preset values for the parameters T
H
and T
L
in topic Time response (Page 124).
The actual value of another, already-configured function can provide the on-delay and off-
delay times for parameters T
H
and T
L
. ou can use the actual values of the following functions:
Analog comparator (Page 183)(actual value Ax - Ay)
Analog trigger (Page 178)(actual value Ax)
Analog amplifier (Page 191)(actual value Ax)
Analog multiplexer (Page 209)(actual value A)
Analog ramp control (Page 212)(actual value A)
Analog Math (Page 224)(actual value A)
PI controller (Page 216)(actual value A)
Up/down counter (Page 168)(actual value Cnt)
Analog filter (Page 229) (actual value A)
Average value (Page 235) (actual value A)
Max/Min (Page 231) (actual value A)
On-delay (Page 132)(current time Ta)
Off-delay (Page 136)(current time Ta)
On-/off-delay (current time Ta)
Retentive on-delay (Page 140)(current time Ta)
Symbol in
IDEC SmartRelay
iring Description
Input Trg A positive edge (0 to 1 transition) at input Trg (Trigger)
triggers the on-delay time T
H
.
A negative edge (1 to 0 transition) at input Trg
(Trigger) triggers the off-delay time T
L
.
Parameter T
H
is the time after which the output is set hi (output
signal transition 0 to 1).
T
L
is the time after which the output is reset ( output
signal transition 1 to 0).
Retentivity:
/  No retentivity
R  The status is retentive.
Output  IDEC SmartRelay sets  when the configured time T
H
expires and Trg is still set. IDEC SmartRelay resets 
when T
L
expires, if the trigger Trg has not been set.
4
7UJ
3DU
2Q2II'HOD\
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Other manuals for IDEC SMARTRELAY

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC SMARTRELAY and is the answer not in the manual?

IDEC SMARTRELAY Specifications

General IconGeneral
BrandIDEC
ModelSMARTRELAY
CategoryOther
LanguageEnglish

Related product manuals