4.4 Special functions list - SF
4.4.16 Operating hours counter
Short description
A configured time is triggered with a signal at the monitoring input. The output is set when this
time has expired.
Symbol in IDEC
SmartRelay
iring Description
Input R A positive edge (0 to 1 transition) at input R resets
output and sets a configured value MI at the counter
for the duration of the time-to-go (MN).
Input En En is the monitoring input. IDEC SmartRelay scans
the on-time of this input.
Input Ral A positive edge at input Ral (Reset all) resets the
operating hours counter (OT) and the output, and sets
the time-to-go value (MN) to the maintenance interval
MI:
Output   0
Measured operating time OT  0
Time-to-go of the maintenance interval MN  MI.
Parameter MI: Maintenance interval to be preset in units of hours
and minutes
Range of values:
0000 h to 9999 h, 0 m to 59 m
OT: the accumulated total operating time (you can
specify an offset in hours and minute)
Range of values:
00000 h to 99999 h, 0 m to 59 m
0 occurs depending on the following conditions:
hen R is selected:
  1, if MN  0
  0, if R  1 or Ral  1
hen REn is selected:
  1, if MN  0
  0, if R  1 or Ral  1 or En  0.
Output  The output is set when the time-to-go MN  0 (see
timing diagram).
The output is reset under the following conditions:
hen  0:REn, if
R  1 or Ral  1 or En  0
hen  0:R, if R  1 or Ral  1.
Note
MI, MN and OT are always retentive.