Technical data
A.11 Technical data: FL1F-K2BM2
IDEC SmartRelay Manual
300
A.11 Technical data: FL1F-K2BM2
FL1F-K2BM2
Power supply
Input voltage 24VDC
Permissible range 20.4VDC to 28.8 VDC
Power consumption 15mA to 82 mA
Voltage failure buffering Typ. 10 ms
Power loss at 24 VDC 0.4W to 2.0 W
Electrical isolation No
Reverse polarity protection Yes
Ground terminal For connecting ground and shielding of the analog
output line.
Analog outputs
Number 2
Voltage range 0VDC to 10 VDC
Voltage load 5 kΩ
Current output 0/4mA to 20 mA
Curreny load 250 Ω
Resolution 10 bit, normalized to 0 to 1000
Cycle time for analog output Depending on installation (50 ms)
Electrical isolation No
Line length (shielded and twisted) Max. 10 m
Error limit Voltage output: ± 2.5% FS
Short circuit protection Voltage output: Yes
Overload protection Current output: Yes
Voltage output: Yes