EasyManua.ls Logo

IDEC SMARTRELAY

IDEC SMARTRELAY
338 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IDEC SmartRelay Manual
235
IDEC SmartRelay functions
4.4 Special functions list - SF
4.4.36 Average value
Short description
The average value function calculates the average value of an analog input over a configured
time period.
Symbol in
IDEC SmartRelay
iring Description
En A change in status from 0 to 1 transition at input En
starts the average value function.
A change in status from 1 to 0 at input En holds the
analog output value.
R A signal at input R clears the analog output value.
Ax Input Ax is one of the following analog signals:
AI1 to AI8 ()
AM1 to AM64
NAI1 to NAI32
A1 to A8
NA1 to NA16
Block number of a function with analog output
Parameter St (Sampling time): you can set the timebase to s
(seconds), d (days), h (hours), or m (minutes).
Range of values:
St  s: 1 to 59
St  d: 1 to 365
St  h: 1 to 23
St  m: 1 to 59
Sn (Number of samples):
Range of values:
St  s: 1 to St100
St  d: 1 to 32767
St  h: 1 to 32767
St  m and St  5 minutes: 1 to St6000
St  m and St  6 minutes: 1 to 32767
Retentivity:
/  no retentivity
R  retentivity
Output A Outputs the average value of input Ax over configured
time sampling period.
 AI1 to AI8: 0 V to 10 V corresponds with 0 to 1000 (internal value).
$4
$[
(Q
5
$[
3D
U
$YHUDJH9DOXH