IDEC SmartRelay functions
4.4 Special functions list - SF
IDEC SmartRelay Manual
144
4.4.6 Edge-triggered interval time-delay relay
Short description
An input pulse generates a preset number of output pulses with a defined pulse/pause ratio
(retriggerable), after a configured delay time has expired.
Parameters TH and TL
Note the information on parameter T in topic Time response (Page 124).
The actual value of another already-programmed function can provide the pulse width TH and
the interpulse width TL. ou can use the actual values of the following functions:
Analog comparator (Page 183)(actual value Ax  Ay)
Analog trigger (Page 178)(actual value Ax)
Analog amplifier (Page 191)(actual value Ax)
Analog multiplexer (Page 209)(actual value A)
Analog ramp control (Page 212)(actual value A)
Analog Math (Page 224)(actual value A)
PI controller (Page 216)(actual value A)
Up/down counter (Page 168)(actual value Cnt)
Analog filter (Page 229) (actual value A)
Average value (Page 235) (actual value A)
Max/Min (Page 231) (actual value A)
On-delay (Page 132) (current time Ta)
Off-delay (Page 136) (current time Ta)
On-/off-delay (Page 138) (current time Ta)
Retentive on-delay (Page 140) (current time Ta)
Interval time-delay relay/Pulse output (Page 142) (current time Ta)
Edge-triggered interval time-delay relay (Page 144) (current time Ta)
Symbol in IDEC
SmartRelay
iring Description
Input Trg A signal at input Trg (Trigger) triggers the times for the
edge-triggered interval time-delay relay.
Input R A signal at input R resets the current time (T
a
) and the
output.
Parameter The interpulse width T
L
and the pulse width T
H
are
configurable.
N determines the number of pulse/pause cycles TL/
TH:
Range of values: 1...9
Retentivity:
/  No retentivity
R  The status is retentive.
Output   is set after TL expires, and reset after TH expires.
4
7UJ
5
3D
U
(7,17
7LPH'HOD\
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Other manuals for IDEC SMARTRELAY

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC SMARTRELAY and is the answer not in the manual?

IDEC SMARTRELAY Specifications

General IconGeneral
BrandIDEC
ModelSMARTRELAY
CategoryOther
LanguageEnglish

Related product manuals