Page: D-1
JFS-A1 INSTALLATION, OPERATION, AND INSTRUCTION MANUAL
Document # : DOC230
Issued: August 27, 2012
Revised: N/A
AppendixD:PSN-1000/PSN-1000(E)MaintenanceandTesting
e power supply board has one fuse on the board for the AC power over current protection.
e AC fuse is rated at 8A 250VAC Time-Lag and screened onto the main board as F1.
e batteries are to be replaced at least once every four years. e batteries are required to be UL recognized
batteries with a date of manufacture permanently marked on the battery. e battery is to be tested at least annually
and if the battery is showing signs of failure, it is to be replaced.
e battery is to remain in the cabinet with nothing on or around the batteries. Only properly sized sealed lead acid
batteries are to be used with the control panel. Use of another battery or not providing the proper clearance may
result in a re or an explosions.
e PSN-1000 is required to be installed in accordance with local and state building codes and NFPA 72 (National
Fire Alarm Code).
e PSN-1000 and related system is required to be inspected and tested in accordance with NFPA 72.
De-Energize Unit Prior to Servicing!