Page: 38
JFS-A1 INSTALLATION, OPERATION, AND INSTRUCTION MANUAL
Document #: DOC230
Issued: August 27, 2012
Revised: N/A
Section 5: Programming
is section addresses programming options and their parameters, provides an overview of the programming process,
and addresses how to use the two programming methods: (1)the LEARN function, and (2) the remote computer
programming process.
is section also includes procedures on uploading and downloading conguration data using the panel conguration
software. Please refer to this section to learn how to navigate within the software, access and modify programming
settings, such as the system clock and day/night mode sensitivity settings, scheduling holidays, displaying events,
and programming optional modules (i.e., DACT, remote annunciators and a Class A card).
Programming Options
Table 9: Programming Options
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
Misc
Idle LCD
Message
Y Yes/No All settings allowed
Misc Display Events Y
Initial Event
Newest Event
Initial Event
Auto display of
rst event
Misc SLC Blink Y Normal/Slow/Off All settings allowed
Misc
Alarm
Verication Time
Y 0-60 Sec All settings allowed
Misc Waterow Delay Y 0-255 Sec 0-90 sec
Misc
AC Report
Delay
Y 0-30 Hours 1-3 Hours
For UL864 use
1-3 Hr
Misc
DH Low AC
Dropout Delay
Y
No delay, 15 sec, 1 minute,
5 minute
All settings allowed
Misc Auto Test Time Y Time of Day All settings allowed
Misc
Strobes Active
When Silenced
Y Yes/No All settings allowed
Misc 50 Hz AC Y Yes/No All settings allowed
Misc Display AM/PM Y AM/PM, 24 Hour All settings allowed
Misc Time Zone Y 24 Time Zone Selections All settings allowed
Misc DST Enabled Y Yes/No All settings allowed
To users, installers, authorities having jurisdiction, and other involved parties:
is product incorporates eld-programmable software. In order for the
product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming
features or options must be limited to specic values or not used at all as
indicated below.