JFS-A1 INSTALLATION, OPERATION, AND INSTRUCTION MANUAL
Document # : DOC230
Issued: August 27, 2012
Revised: N/A
Table 9: Programming Options
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
Misc DST Start Y Month/Day All settings allowed
Misc DST End Y Month/Day All settings allowed
Zone Zone Type Y
Alarm
Supervisory
Positive Alarm Sequence
Auxiliary
Releasing
Fire Drill
System Alarm
System Supervisory
System Trouble
All settings allowed
Zone Alarm Count Y 1-10 All settings allowed
Zone Silenceable Y Yes/No All settings allowed
Zone Silence Inhibit Y Yes/No All settings allowed
Zone Auto Silence Y Yes/No All settings allowed
Zone Auto Unsilence Y Yes/No All settings allowed
Zone Restore Delay Y 0-300 Sec Full range allowed
Zone Latching Y Yes/No All settings allowed
Zone Local Y Yes/No All settings allowed
Zone Output Pattern Y
Constant
ANSI Temporal
March Code
Double Time
All settings allowed
Zone Day Sensitivity Y 1.1%-3.5% Full range allowed
Within listed range
of sensor
Zone Night Sensitivity Y 1.1%-3.5% Full range allowed
Within listed range
of sensor
Zone
Fixed Heat
Setting
Y
135
F-185F
Full range allowed
Within listed range
of sensor
Zone
Combo ROR/
Fixed Setting
Y
135
F-174F
All settings allowed
Within listed range
of sensor
Releasing Abort Type Y ULI, IRI, AHJ, NYC ULI
Only ULI is
permitted in UL
installations
Releasing
Pre-Release
Timer
Y 0-60 Sec Full range allowed
Length of time of
pre-release
Releasing
Pre-Release
Pattern
Y
Constant
ANSI Temporal
March Code
Double Time
All settings allowed
Pattern from NAC
during Pre-
Release
Releasing
Manual Release
Timer
Y 0-30 Sec Full range allowed
Length of time of
Pre-Release
Releasing
Manual Release
Abort Allowed
Y Yes/No All settings allowed
Species whether
Man-Release is
Cancellable