JFS-A1 INSTALLATION, OPERATION, AND INSTRUCTION MANUAL
Document # : DOC230
Issued: August 27, 2012
Revised: N/A
Two Count Releasing Application with Abort Switch
is releasing application requires the activation of two sensors or a manual release input within a designated
releasing zone to start the release sequence. e timing of the release can be aected by the operation of an abort
input within the designated releasing zone.
Activation of an input module classied for the abort switch function will initiate the abort type sequence as selected
in programming. e abort switch must be pressed prior to the pre-discharge timer expires as programmed.
Note: Any device being used to initiate the abort function should be clearly marked and or labeled.
Figure 106. Example of Two Count Releasing Application with Abort Switch
Zone 1: Releasing
1
2
NAC Release
Solenoid
Smoke
Detector
Heat Combo
Abort Switch
Cross Zone Releasing Application with Abort Switch
is releasing application requires the activation of at least one sensor within each of the designated “Cross Zones”
or a manual release within the designated release zone to start the release sequence. e timing of the release can be
aected by the operation of an abort input within the designated releasing zone.
Activation of an input module classied for the abort switch function will initiate the abort type sequence as selected
in programming. e abort switch must be pressed prior to the pre-discharge timer expires as programmed.
Note: Any device being used to initiate the abort function should be clearly marked and or labeled.
Figure 107. Example of Cross Zone Releasing Application with Abort Switch
Zone 1: Alarm
1
Addr Heat
Combo Detector
Zone 2: Alarm
2
Addr Photo
Heat Detector
NAC Release
Solenoid
Zone 3: Releasing
Abort
Switch
Symbol Legend:
= SLC Input
= SLC Output
= Panel Input (I/O)