JFS-A1 INSTALLATION, OPERATION, AND INSTRUCTION MANUAL
Document #: DOC230
Issued: August 27, 2012
Revised: N/A
Table 9: Programming Options
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
Releasing Soak Time Y 0-20 Minutes Full range allowed
Length of time the
release circuit is
active post release
SLC Point Function Y
Photo Detector (PSA)
Photo Duct Detector (DSA)
Photo/Heat Detector
(PSHA)
Fixed Heat Detector (FHA)
Combination Fixed / ROR
Heat Detector (RHA)
Conv. Zone Module (CIZM)
Mini Contact Mod (MCM)
Single Contact Mod (SCM)
Dual Contact Mod (DCM)
Mon. Output Mod (MOM)
Twin Relay Module (TRM)
Sounder Base (ASB)
Relay Base (ARB)
All settings allowed
Species use/type
of SLC device
SLC Point
Dry Contact
Input Functions
Y
Pull Station, Water Flow,
Supervisory, Tamper, Fire
Drill, Trouble Monitor, Aux,
Abort, Reset, Silence
All settings allowed
Applies to all
dry-contact input
devices and
circuits.
SLC Point Alarm Verif Y Yes/No All settings allowed
SLC Point Supervisory Y Yes/No All settings allowed
NACs Function
Potter/Amseco Sync
Gentex Sync
System Sensor Sync
Wheelock Sync
Constant Output
Resettable Output
Door Holder Output
ANSI Output
City Tie Output
Release / Solenoid Output
All settings allowed
Species use of
NAC circuit(s)
Day/Night
Smoke
Sensitivity
Y
Full listed range of
smoke detector
All settings allowed
Up to 50 holidays
where day mode is
not active.
DACT Daily Test Call Y Any time of day All settings allowed
Alternates
between line 1 and
2 if line 2
is enabled.
E-Mail
E-mail Status
Reports
N
Alarms, Troubles,
Supervisory Test, History &
Status Reports
IP-Dialer
IP Based
Central Station
Reporting
Y
Alarms, Supervisory,
Trouble & Test Reports
All settings allowed