76 VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Chapter 6 — PID Application
Code Parameter Min. Max. Unit Default ID Note
P7.3.2.9
PID1 Set Point 1 Boost -2.0 2.0 1.0 1320
P7.3.2.10
PID1 Set Point 1 Comp Enable 0 1352 See Par ID 1346
P7.3.2.11
PID1 Set Point 1 Comp Max -200.00 200.00 % 0.00 1353
Table 97. Setpoint 2 — P7.3.3
Code Parameter Min. Max. Unit Default ID Note
P7.3.3.1
PID1 Set Point 2 Source 2 1321 See Par ID 1312
P7.3.3.2
PID1 Set Point 2 Min -200.00 200.00 % 0.00 1322
P7.3.3.3
PID1 Set Point 2 Max -200.00 200.00 % 100.00 1323
P7.3.3.4
PID1 Set Point 2 Sleep Enable 0 1324 See Par ID 1346
P7.3.3.5
PID1 Set Point 2 Sleep Unit Sel 0 2397 See Par ID 2396
P7.3.3.6
PID1 Set Point 2 Sleep Level Varies 0.00 2452
P7.3.3.7
PID1 Set Point 2 Sleep Delay 0 3000 s 0 1326
P7.3.3.8
PID1 Set Point 2 Wake Up Level -99999.99 99999.99 Varies 0.00 1327
P7.3.3.9
PID1 Set Point 2 Boost -2.0 2.0 1.0 1329
P7.3.3.10
PID1 Set Point 2 Comp Enable 0 1354 See Par ID 1346
P7.3.3.11
PID1 Set Point 2 Comp Max -200.00 200.00 % 0.00 1355
Feedback
Table 98. Basic — P7.4.1
Code Parameter Min. Max. Unit Default ID Note
P7.4.1.1
PID1 Feedback Function 0 1330 0 = Source 1
1 = SQRT(Source 1)
2 = SQRT(Source 1 - Source 2)
3 = SQRT(Source 1) + SQRT(Source 2)
4 = Source 1 + Source 2
5 = Source 1 - Source 2
6 = MIN(Source 1,Source 2)
7 = MAX(Source 1,Source 2)
8 = MEAN(Source1,Source2)
P7.4.1.2
PID1 Feedback Gain -1000.0 1000.0 % 100.0 1331
ote: N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.
Table 96. Setpoint 1 — P7.3.2, continued