44
Chapter 5—Basic application
VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Table 39. Analog Output 2 — P3.4
Code Parameter Min. Max. Unit Default ID Note
P4.4.1
Currency 0 2122 0 = $
1 = £
2 = €
3 = ¥
4 = Rs
5 = R$
6 = Fr
7 = kr
P4.4.2
Energy Cost Varies 0.00 2123
P4.4.3
Data Type 0 2124 0 = Cumulative
1 = Daily Avg
2 = Weekly Avg
3 = Monthly Avg
4 = Yearly Avg
P4.4.4 Energy Savings Reset 2125 0 = Not Reset
1 = Reset
Motor Control
Table 40. Basic Setting — P5.1
Code Parameter Min. Max. Unit Default ID Note
P5.1.1
Motor Control Mode 0 287 0 = Freq Control
1 = Speed Control
P5.1.2
Current Limit DriveNomCurrCT*1/10 DriveNomCurrCT*2 A DriveNomCurrCT*2 107
P5.1.3
V/Hz Optimization 0 109 See Par ID 1679
P5.1.4
V/Hz Ratio 3 108 0 = Linear
1 = Squared
2 = Programmable
3 = Linear + Flux
Optimization
P5.1.5
Field Weakening Point 8.00 400.00 Hz Varies 289
P5.1.6
Voltage at FWP 10.00 200.00 % 100.00 290
P5.1.7
V/Hz Mid Frequency 0.00 See Par ID 289 Hz Varies 291
P5.1.8
V/Hz Mid Voltage 0.00 100.00 % 100.00 292
P5.1.9
Zero Frequency Voltage 0.00 40.00 % 0.00 293
P5.1.10
Switching Frequency MinSwitchFreq MaxSwitchFreq kHz DefaultSwitchFreqCT 288
P5.1.11
Sine Filter Enable 0 1665 See Par ID 1679
P5.1.12
OverVoltage Control 1 294 See Par ID 1679
Protections
Table 41. Motor — P6.1
Code Parameter Min. Max. Unit Default ID Note
P6.1.1
Output Phase Fault 2 308 0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
P6.1.2
Ground Fault 2 309 See Par ID 308
P6.1.3
Ground Fault Limit 0 30 % 15 2158
P6.1.4
Motor Thermal
Protection
2 310 See Par ID 308
P6.1.5
Motor Thermal F0
Current
0.0 150.0 % 40.0 311
otes: N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.