44
Chapter 5—Basic application
VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Table 39. Analog Output 2 — P3.4
Code Parameter Min. Max. Unit Default ID Note
P4.4.1
Currency 0 2122 0 = $
1 = £
2 = €
3 = ¥
4 = Rs
5 = R$
6 = Fr
7 = kr
P4.4.2
Energy Cost Varies 0.00 2123
P4.4.3
Data Type 0 2124 0 = Cumulative
1 = Daily Avg
2 = Weekly Avg
3 = Monthly Avg
4 = Yearly Avg
P4.4.4 Energy Savings Reset 2125 0 = Not Reset
1 = Reset
Motor Control
Table 40. Basic Setting — P5.1
Code Parameter Min. Max. Unit Default ID Note
P5.1.1

Motor Control Mode 0 287 0 = Freq Control
1 = Speed Control
P5.1.2
Current Limit DriveNomCurrCT*1/10 DriveNomCurrCT*2 A DriveNomCurrCT*2 107
P5.1.3

V/Hz Optimization 0 109 See Par ID 1679
P5.1.4

V/Hz Ratio 3 108 0 = Linear
1 = Squared
2 = Programmable
3 = Linear + Flux
Optimization
P5.1.5

Field Weakening Point 8.00 400.00 Hz Varies 289
P5.1.6

Voltage at FWP 10.00 200.00 % 100.00 290
P5.1.7

V/Hz Mid Frequency 0.00 See Par ID 289 Hz Varies 291
P5.1.8

V/Hz Mid Voltage 0.00 100.00 % 100.00 292
P5.1.9

Zero Frequency Voltage 0.00 40.00 % 0.00 293
P5.1.10
Switching Frequency MinSwitchFreq MaxSwitchFreq kHz DefaultSwitchFreqCT 288
P5.1.11
Sine Filter Enable 0 1665 See Par ID 1679
P5.1.12

OverVoltage Control 1 294 See Par ID 1679
Protections
Table 41. Motor — P6.1
Code Parameter Min. Max. Unit Default ID Note
P6.1.1

Output Phase Fault 2 308 0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
P6.1.2

Ground Fault 2 309 See Par ID 308
P6.1.3
Ground Fault Limit 0 30 % 15 2158
P6.1.4

Motor Thermal
Protection
2 310 See Par ID 308
P6.1.5
Motor Thermal F0
Current
0.0 150.0 % 40.0 311
otes: N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VS3 Series and is the answer not in the manual?

Johnson Controls VS3 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVS3 Series
CategoryInverter
LanguageEnglish

Related product manuals