118 VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Chapter 7—Advanced application parameter
Table 182. Monitor — P8.2
Code Parameter Min. Max. Unit Default ID Note
P8.2.1
PID2 Wake Up Action 0 2467 See Par ID 2466
P8.2.2 FB PID2 Set Point 1 See Par ID 1298 See Par ID 1300 Varies 2546
P8.2.3 FB PID2 Set Point 2 See Par ID 1298 See Par ID 1300 Varies 2548
P8.2.4 FB PID2 Feedback 1 % 2552
P8.2.5 FB PID2 Feedback 2 % 2553
P8.2.6 FB PID2 Feedforward 1 % 2556
P8.2.7 FB PID2 Feedforward 2 % 2557
Setpoint
Table 183. Basic — P8.3.1
Code Parameter Min. Max. Unit Default ID Note
P8.3.1.1
PID2 Keypad Set Point 1 See Par ID 1360 See Par ID 1362 Varies 0.00 1369
P8.3.1.2
PID2 Keypad Set Point 2 See Par ID 1360 See Par ID 1362 Varies 0.00 1371
P8.3.1.3
PID2 Wake Up Action 0 2467 See Par ID 2466
Table 184. Setpoint 1 — P8.3.2
Code Parameter Min. Max. Unit Default ID Note
P8.3.2.1

PID2 Set Point 1 Source 1 1374 0 = Not Used
1 = PID2 Keypad Set Point 1
2 = PID2 Keypad Set Point 2
3 = AI1
4 = AI2
5 = Slot A: AI1
6 = Slot B: AI1
7 = FB Process Data Input 1
8 = FB Process Data Input 2
9 = FB Process Data Input 3
10 = FB Process Data Input 4
11 = FB Process Data Input 5
12 = FB Process Data Input 6
13 = FB Process Data Input 7
14 = FB Process Data Input 8
15 = PID1 Output
16 = FB PID2 Set Point 1
17 = FB PID2 Set Point 2
P8.3.2.2
PID2 Set Point 1 Min -200.00 200.00 % 0.00 1375
P8.3.2.3
PID2 Set Point 1 Max -200.00 200.00 % 100.00 1376
P8.3.2.4

PID2 Set Point 1 Sleep Enable 0 1377 See Par ID 1346
P8.3.2.5

PID2 Set Point 1 Sleep Unit Sel 0 2398 0 = Output Frequency
1 = Motor Speed
2 = Motor Current
3 = PID2 Feedback
P8.3.2.6
PID2 Set Point 1 Sleep Level Varies 0.00 2454
P8.3.2.7
PID2 Set Point 1 Sleep Delay 0 3000 s 0 1379
P8.3.2.8
PID2 Set Point 1 WakeUp
Level
-99999.99 99999.99 Varies 0.00 1380
P8.3.2.9
PID2 Set Point 1 Boost -2.0 2.0 1.0 1382
P8.3.2.10
PID2 Set Point1 Comp Enable 0 1414 See Par ID 1346
P8.3.2.11
PID2 Set Point1 Comp Max -200.00 200.00 % 0.00 1415
P8.3.2.12 FB PID2 Set Point 1 See Par ID 1298 See Par ID 1300 Varies 2546
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VS3 Series and is the answer not in the manual?

Johnson Controls VS3 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVS3 Series
CategoryInverter
LanguageEnglish

Related product manuals