118 VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Chapter 7—Advanced application parameter
Table 182. Monitor — P8.2
Code Parameter Min. Max. Unit Default ID Note
P8.2.1
PID2 Wake Up Action 0 2467 See Par ID 2466
P8.2.2 FB PID2 Set Point 1 See Par ID 1298 See Par ID 1300 Varies 2546
P8.2.3 FB PID2 Set Point 2 See Par ID 1298 See Par ID 1300 Varies 2548
P8.2.4 FB PID2 Feedback 1 % 2552
P8.2.5 FB PID2 Feedback 2 % 2553
P8.2.6 FB PID2 Feedforward 1 % 2556
P8.2.7 FB PID2 Feedforward 2 % 2557
Setpoint
Table 183. Basic — P8.3.1
Code Parameter Min. Max. Unit Default ID Note
P8.3.1.1
PID2 Keypad Set Point 1 See Par ID 1360 See Par ID 1362 Varies 0.00 1369
P8.3.1.2
PID2 Keypad Set Point 2 See Par ID 1360 See Par ID 1362 Varies 0.00 1371
P8.3.1.3
PID2 Wake Up Action 0 2467 See Par ID 2466
Table 184. Setpoint 1 — P8.3.2
Code Parameter Min. Max. Unit Default ID Note
P8.3.2.1
PID2 Set Point 1 Source 1 1374 0 = Not Used
1 = PID2 Keypad Set Point 1
2 = PID2 Keypad Set Point 2
3 = AI1
4 = AI2
5 = Slot A: AI1
6 = Slot B: AI1
7 = FB Process Data Input 1
8 = FB Process Data Input 2
9 = FB Process Data Input 3
10 = FB Process Data Input 4
11 = FB Process Data Input 5
12 = FB Process Data Input 6
13 = FB Process Data Input 7
14 = FB Process Data Input 8
15 = PID1 Output
16 = FB PID2 Set Point 1
17 = FB PID2 Set Point 2
P8.3.2.2
PID2 Set Point 1 Min -200.00 200.00 % 0.00 1375
P8.3.2.3
PID2 Set Point 1 Max -200.00 200.00 % 100.00 1376
P8.3.2.4
PID2 Set Point 1 Sleep Enable 0 1377 See Par ID 1346
P8.3.2.5
PID2 Set Point 1 Sleep Unit Sel 0 2398 0 = Output Frequency
1 = Motor Speed
2 = Motor Current
3 = PID2 Feedback
P8.3.2.6
PID2 Set Point 1 Sleep Level Varies 0.00 2454
P8.3.2.7
PID2 Set Point 1 Sleep Delay 0 3000 s 0 1379
P8.3.2.8
PID2 Set Point 1 WakeUp
Level
-99999.99 99999.99 Varies 0.00 1380
P8.3.2.9
PID2 Set Point 1 Boost -2.0 2.0 1.0 1382
P8.3.2.10
PID2 Set Point1 Comp Enable 0 1414 See Par ID 1346
P8.3.2.11
PID2 Set Point1 Comp Max -200.00 200.00 % 0.00 1415
P8.3.2.12 FB PID2 Set Point 1 See Par ID 1298 See Par ID 1300 Varies 2546
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.