115VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Chapter 7—Advanced application parameter
Table 173. Setpoint 1 — P7.3.2
Code Parameter Min. Max. Unit Default ID Note
P7.3.2.1
PID1 Set Point 1 Source 1 1312 0 = Not Used
1 = PID1 Keypad Set Point 1
2 = PID1 Keypad Set Point 2
3 = AI1
4 = AI2
5 = Slot A: AI1
6 = Slot B: AI1
7 = FB Process Data Input 1
8 = FB Process Data Input 2
9 = FB Process Data Input 3
10 = FB Process Data Input 4
11 = FB Process Data Input 5
12 = FB Process Data Input 6
13 = FB Process Data Input 7
14 = FB Process Data Input 8
15 = PID2 Output
16 = FB PID1 Set Point 1
17 = FB PID1 Set Point 2
P7.3.2.2
PID1 Set Point 1 Min -200.00 200.00 % 0.00 1313
P7.3.2.3
PID1 Set Point 1 Max -200.00 200.00 % 100.00 1314
P7.3.2.4
PID1 Set Point 1 Sleep Enable 0 1315 See Par ID 1346
P7.3.2.5
PID1 Set Point 1 Sleep Unit Sel 0 2396 0 = Output Frequency
1 = Motor Speed
2 = Motor Current
3 = PID1 Feedback
P7.3.2.6
PID1 Set Point 1 Sleep Level Varies 0.00 2450
P7.3.2.7
PID1 Set Point 1 Sleep Delay 0 3000 s 0 1317
P7.3.2.8
PID1 Set Point 1 Wake
Up Level
-99999.99 99999.99 Varies 0.00 1318
P7.3.2.9
PID1 Set Point 1 Boost -2.0 2.0 1.0 1320
P7.3.2.10
PID1 Set Point 1 Comp Enable 0 1352 See Par ID 1346
P7.3.2.11
PID1 Set Point 1 Comp Max -200.00 200.00 % 0.00 1353
Table 174. Setpoint 2 — P7.3.3
Code Parameter Min. Max. Unit Default ID Note
P7.3.3.1
PID1 Set Point 2 Source 2 1321 See Par ID 1312
P7.3.3.2
PID1 Set Point 2 Min -200.00 200.00 % 0.00 1322
P7.3.3.3
PID1 Set Point 2 Max -200.00 200.00 % 100.00 1323
P7.3.3.4
PID1 Set Point 2 Sleep Enable 0 1324 See Par ID 1346
P7.3.3.5
PID1 Set Point 2 Sleep Unit Sel 0 2397 See Par ID 2396
P7.3.3.6
PID1 Set Point 2 Sleep Level Varies 0.00 2452
P7.3.3.7
PID1 Set Point 2 Sleep Delay 0 3000 s 0 1326
P7.3.3.8
PID1 Set Point 2 Wake Up
Level
-99999.99 99999.99 Varies 0.00 1327
P7.3.3.9
PID1 Set Point 2 Boost -2.0 2.0 1.0 1329
P7.3.3.10
PID1 Set Point 2 Comp Enable 0 1354 See Par ID 1346
P7.3.3.11
PID1 Set Point 2 Comp Max -200.00 200.00 % 0.00 1355
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.