43
Chapter 5—Basic application
VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Drive Control
Table 36. Basic Setting — P4.1
Code Parameter Min. Max. Unit Default ID Note
P4.1.1
Keypad Reference See Par ID 101 See Par ID 102 Hz 0.00 141
P4.1.2
Keypad Direction 0 116 0 = Forward
1 = Reverse
P4.1.3
Keypad Stop 1 114 0 = Enabled-Keypad Operation
1 = Always Enabled
P4.1.4
Hand Key Enable 0 1724 0 = Enabled
1 = Disabled
P4.1.5
Reverse Enable 1 1679 0 = Disabled
1 = Enabled
P4.1.6 Change PhaseSequence
Motor
0 2515 0 = Change Disable
1 = Change Enable
P4.1.7
Power Up HOA Select 0 1685 0 = Hold Last
1 = Hand Control
2 = Auto control
3 = Off
P4.1.9
Run Delay Time 0 32500 s 0 2423
P4.1.10
Start Mode 0 252 0 = Ramp
1 = Flying Start
P4.1.11
Stop Mode 0 253 0 = Coasting
1 = Ramp
P4.1.12
Ramp 1 Shape 0.0 10.0 s 0.0 247
P4.1.13
Ramp 2 Shape 0.0 10.0 s 0.0 248
P4.1.14
Accel Time 2 0.1 3000.0 s 10.0 249
P4.1.15
Decel Time 2 0.1 3000.0 s 10.0 250
P4.1.16
Power Loss Function 0 267 See Par ID 1679
P4.1.17
Power Loss Time 0.3 5.0 s 2.0 268
P4.1.18

2nd Stage Ramp Frequency See Par ID 101 See Par ID 102 Hz 30.00 2444
Table 37. Brake — P4.2
Code Parameter Min. Max. Unit Default ID Note
P4.2.1

DC-Brake Current DriveNomCurrCT*15/100 DriveNomCurrCT*15/10 A DriveNomCurrCT*1/2 254
P4.2.2

Start DC-Brake Time 0.00 600.00 s 0.00 263
P4.2.3

Stop DC-Brake Frequency 0.10 10.00 Hz 1.50 262
P4.2.4

Stop DC-Brake Time 0.00 600.00 s 0.00 255
P4.2.5

Brake Chopper Define 0 251 0 = Disabled
1 = B(Run) T(Rdy)
2 = External
3 = B(Rdy) T(Rdy)
4 = B(Run) T(No)
P4.2.6

Flux Brake 0 = Off
1 = On
P4.2.7

Flux Brake Current ActiveMotorNomCurr*1/10 See Par ID 107 A ActiveMotorNomCurr*1/2 265
Table 38. Skip Frequency — P4.3
Code Parameter Min. Max. Unit Default ID Note
P4.3.1
Skip Range Ramp Factor 0.1 10.0 1.0
264
P4.3.2
Skip F1 Low Limit
0.00 See Par ID 257 Hz 0.00
256
P4.3.3
Skip F1 High Limit See Par ID 256 400.00 Hz 0.00
257
P4.3.4
Skip F2 Low Limit 0.00 See Par ID 259 Hz 0.00
258
P4.3.5
Skip F2 High Limit See Par ID 258 400.00 Hz 0.00
259
P4.3.6
Skip F3 Low Limit 0.00 See Par ID 261 Hz 0.00 260
P4.3.7
Skip F3 High Limit See Par ID 260 400.00 Hz 0.00 261
otes: N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VS3 Series and is the answer not in the manual?

Johnson Controls VS3 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVS3 Series
CategoryInverter
LanguageEnglish

Related product manuals