124 VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Chapter 7—Advanced application parameter
Table 202. FB Process Data Output Sel — P12.2, continued
Code Parameter Min. Max. Unit Default ID Note
P12.2.9
Standard Status Word Bit0
Function Select (cont.)
1 2415 26 = In Bypass Mode
27 = Ext Fault/Warning
28 = Auto Control
29 = Jog Speed Select
30 = Motor Therm Protection
31 = FB Digital Input 1
32 = FB Digital Input 2
33 = FB Digital Input 3
34 = FB Digital Input 4
35 = Damper Control
36 = TC1 Status
37 = TC2 Status
38 = TC3 Status
40 = Power Limit Superv
41 = Temp Limit Superv
42 = Analog Input Superv
43 = Motor 1 Control
48 = Logic Fulfilled
49 = PID1 Sleep
50 = PID2 Sleep
51 = Motor Current 1 Supv
52 = Motor Current 2 Supv
53 = Second AI Limit Supv
54 = DC Charge Switch Close
55 = Preheat Active
56 = Cold Weather Active
58 = 2th Stage Ramp Frequency
Active
59 = STO Fault Output
60 = Run Bypass/Drive
61 = Bypass Overload
62 = Bypass Run
P12.2.10
Standard Status Word Bit1
Function Select
22416See Par ID 2415
P12.2.11
Standard Status Word Bit2
Function Select
32417See Par ID 2415
P12.2.12
Standard Status Word Bit3
Function Select
42418See Par ID 2415
P12.2.13
Standard Status Word Bit4
Function Select
52419See Par ID 2415
P12.2.14
Standard Status Word Bit5
Function Select
62420See Par ID 2415
P12.2.15
Standard Status Word Bit6
Function Select
72421See Par ID 2415
P12.2.16
Standard Status Word Bit7
Function Select
82422See Par ID 2415
RS485 Bus
Table 203. Basic Setting — P12.3.1
Code Parameter Min. Max. Unit Default ID Note
P12.3.1.1
RS485 Comm Set 0 586 0 = Modbus RTU
1 = BACnet MS/TP
2 = SA Bus
Table 204. Modbus RTU — P12.3.2
Code Parameter Min. Max. Unit Default ID Note
P12.3.2.1
Slave Address 1 247 1 587
P12.3.2.2
Baud Rate 1 584 0 = 9600
1 = 19200
2 = 38400
3 = 57600
4 = 115200
Note:
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VS3 Series and is the answer not in the manual?

Johnson Controls VS3 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVS3 Series
CategoryInverter
LanguageEnglish

Related product manuals