89VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Chapter 6 — PID Application
Code Parameter Min. Max. Unit Default ID Note
P13.1.6 Parameter Comparison 623 0 = No
1 = Compare with Keypad
2 = Compare with Default
3 = Compare with Set 1
4 = Compare with Set 2
P13.1.7 Password 0 9999 0 624
P13.1.8 Parameter Lock 0 625 0 = Change Enable
1 = Change Disable
P13.1.9 Multimonitor Set 0 627 See Par ID 625
P13.1.10 Default Page 0 628 0 = None
1 = Main Menu
2 = Multi-Monitor
3 = Favorite Menu
4 = Keypad Reference
P13.1.11 Timeout Time 0 65535 s 30 629
P13.1.12 Contrast Adjust 5 18 12 630
P13.1.13 Backlight Time 1 65535 min 10 631
P13.1.14 Fan Control 2 632 0 = Continuous
1 = Temperature
2 = Run Follow
3 = Calculate IGBT Temp
P13.1.15 Keypad ACK Timeout 200 5000 ms 200 633
P13.1.16 Keypad Retry Number 1 10 5 634
P13.1.17 Startup Wizard 0 626 0 = Yes
1 = No
P13.1.18
Jog Softkey Hidden 0 2412 See Par ID 1346
P13.1.19
Reverse Softkey Hidden 0 2413 See Par ID 1346
ote: N
Parameter value will be set to be default when changing macros.
Table 132. Basic Setting — P13.1, continued