Appendix A—Description of parameters
VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Code Modbus ID Parameter Application RO/RW
P2.2.26 215 No Access To Param 1,2,3 RW
Use this parameter selecting an external input for locking out the ability to change parameters when this
input is enabled, this can be used with the password protection. When this function is set for Normally
Open it will allow for changing of parameters, if it is set for Normally Closed it prevents any changes to
parameters. If a input is desired to control this DIGIN X can be used. Can be set to DigiIN:X indicates on
board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates
optional board inputs in B slot, or Timer Channel X. RO X Function allows for having an input turn on
without having to hard wire it to the physical relay output.
Closed contact: all writable parameters cannot be edited.
P2.2.27 196 Auto Control 1,2,3 RW
Use this parameter selecting an external input for use when desiring to use the remote control location.
When this function is set for Normally Open the drive will not go into the remote control unless the
keypad input is pressed. When set for Normally Closed the drive will always be in the remote location
no matter the keypad loc/rem is pressed. Can be set to DigiIN:X indicates on board terminal inputs,
DigiIN:A:IOX:X indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in
B slot, or Timer Channel X. RO X Function allows for having an input turn on without having to hard wire
it to the physical relay output.
Closed Contact: force to remote control.
P2.2.28 197 Hand Control 1,2,3 RW
Use this parameter selecting an external input for use when desiring to use the local control location.
When this function is set for Normally Open the drive will not go into the local control place unless
the keypad Loc/Rem button is used. When it is set for Normally Closed it will always be in the local
control location no matter if the keypad loc/rem button is pressed. Can be set to DigiIN:X indicates on
board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates
optional board inputs in B slot, or Timer Channel X. RO X Function allows for having an input turn on
without having to hard wire it to the physical relay output.
Closed contact: force to local control.
P2.2.29 209 Auto 1/2 Select 1,2,3 RW
Use this parameter selecting an external input for use when desiring to use the remote2 control location.
This switches control and reference locations. When this function is set for Normally Open the drive will
not go into the Remote 2 control place and will stay in Remote 1. When it is set for Normally Closed the
drive will always be in the Remote 2 Control Place. When a DIGIN is used it will allow cycling between
the 2 based off high/low state. Can be set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X
indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or
Timer Channel X. RO X Function allows for having an input turn on without having to hard wire it to the
physical relay output.
Closed contact: remote2 is selected as control source.
Open contact: remote1 is selected as control.
P2.2.30 2395 HOA On/Off 1,2,3 RW
Use this parameter for setting external input for disabling any control signal when the input is the off/
open position, when closed drive will follow the desired control signal. If the function is set for Normally
Open this will cause the drive to operate, if the function i set for Normally Closed then the drive will e
in the off location and not allow operation. Can be set to DigiIN: X indicates on board terminal inputs,
DigiIN:A:IOX:X indicates option boards in A slot, DigiIN:B:IOX:X indicates optional board in B slot, or
Timer Channel X. RO X function allows for having an input turn on without having to hard wire it to the
physical relay output.
P2.2.31 217 Second Motor Para Select 2,3 RW
Use this parameter selecting an external input for use of switching between motor parameter set 1(P1
Group) and set 2 (P16 Group). When this function is set for Normally pen the drive will follow the first
set of motor parameters and when the input is set for Normally Closed it will used the Second Motor
Parameter set. If an input is used the function will follow the logic of the input being high/low. Can be
set to DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in A
slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X. RO X Function allows
for having an input turn on without having to hard wire it to the physical relay output.
Closed contact: the 2nd motor parameters is applied.
P2.2.32 2312 Parameter Set1/2 Sel 1,2,3 RW
Use this parameter for setting external input for selecting between the stored parameter set1 or
set2, this requires saving parameters to the stored sets via P21.1.3. When the function is set for
Normally Open the drive will use the standard Parameter Set 1 in the keypad, if the function is set for
Normally Closed the drive will follow Parameter Set 2 setting when stored to the keypad. DigiIN:A:IOX:X
indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or
Timer Channel X. RO X Function allows for having an input turn on without having to hard wire it to the
physical relay output.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VS3 Series and is the answer not in the manual?

Johnson Controls VS3 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVS3 Series
CategoryInverter
LanguageEnglish

Related product manuals