72 VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Chapter 6 — PID Application
Code Parameter Min. Max. Unit Default ID Note
P6.1.15

Thermistor Fault Response 2 333 See Par ID 308
P6.1.16

PT100 Fault Response 2 337 See Par ID 308
P6.1.17
Preheat Mode 0 2159 See Par ID 1346
P6.1.18
Preheat Control Source 31 2160 0 = DigIN:NormallyOpen
1 = DigIN:NormallyClose
2 = DigIN: 1
3 = DigIN: 2
4 = DigIN: 3
5 = DigIN: 4
6 = DigIN: 5
7 = DigIN: 6
8 = DigIN: 7
9 = DigIN: 8
10 = DigIN: A: IO1: 1
11 = DigIN: A: IO1: 2
12 = DigIN: A: IO1: 3
13 = DigIN: A: IO5: 1
14 = DigIN: A: IO5: 2
15 = DigIN: A: IO5: 3
16 = DigIN: A: IO5: 4
17 = DigIN: A: IO5: 5
18 = DigIN: A: IO5: 6
19 = DigIN: B: IO1: 1
20 = DigIN: B: IO1: 2
21 = DigIN: B: IO1: 3
22 = DigIN: B: IO5: 1
23 = DigIN: B: IO5: 2
24 = DigIN: B: IO5: 3
25 = DigIN: B: IO5: 4
26 = DigIN: B: IO5: 5
27 = DigIN: B: IO5: 6
28 = Time Channel 1
29 = Time Channel 2
30 = Time Channel 3
31 = Drive Temperature
32 = SlotA PT100 Temp
Channel 1
33 = SlotA PT100 Temp
Channel 2
34 = SlotA PT100 Temp
Channel 3
35 = SlotA Max PT100 Temp
36 = SlotB PT100 Temp
Channel 1
37 = SlotB PT100 Temp
Channel 2
38 = SlotB PT100 Temp
Channel 3
39 = SlotB Max PT100 Temp
40 = SlotA and SlotB Max
PT100 Temp
P6.1.19
Preheat Enter Temp 0.0 19.9 ˚C 10.0 2161
P6.1.20
Preheat Quit Temp 20.0 40.0 ˚C 20.0 2162
P6.1.21
Preheat Output Volt 0.0 20.0 % 2.0 2163
Table 89. Motor — P6.1, continued
ote: N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.