EasyManua.ls Logo

LSIS LSLV-S100 - Page 289

LSIS LSLV-S100
411 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table of Functions
275
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F SL Ref.
72
22
0h1348
Safe operation
deceleration
time
Q-Stop Time 0.0-600.0(s) 5.0 O/A O I/P p.131
74
23
0h134A
Selection of
regeneration
evasion
function for
press
RegenAvd Sel
0
No
0:No X/A O I p.191
1 Yes
75
23
0h134B
Voltage level of
regeneration
evasion motion
for press
RegenAvd
Level
200V : 300-400V
350
X/A O I p.191
400V : 600-800V 700
76
24
0h134C
Compensation
frequency limit
of regeneration
evasion for
press
CompFreq
Limit
0.00- 10.00Hz
1.00 X/A O I p.191
77
24
0h134D
Regeneration
evasion for
press P gain
RegenAvd
Pgain
0.0- 100.0%
50.0 O/A O I p.191
78
24
0h134E
Regeneration
evasion for
press I gain
RegenAvd
Igain
20-30000(ms)
500 O/A O I p.191
79 0h134F
DB Unit turn on
voltage level
DB Turn On
Lev
200V:
Min
25
~400[V]
390[V]
X/A O I/P -
400V:
Min
25
~800[V]
780[V]
80 0h1350
Fire mode
selection
Fire Mode Sel
0
None
0:None X/A O I/P p.118
1
Fire Mode
2
Fire Mode
Test
81
26
0h1351
Fire mode
frequency
Fire Mode
Freq
0.00~60.00(Hz]
60.00 X/A O I/P p.118
82
26
0h1352
Fire mode
direction
Fire Mode Dir
0
Forward
0:
Forwar
d
X/A O I/P p.118
1 Reverse
83
26
Fire Mode
Count
Fire Mode
Cnt
Can not be
modified
p.118
23
Displayed when dr.09 (Control Mode) is not set to 6 (PM Sensorless).
24
Displayed when Ad.74 is set to 1 (Yes).
25
DC voltage value (convert bA.19 AC Input voltage) + 20V (200V type) or + 40V (400V type)
26
Displayed when Ad.80 is set to 1 (Yes).

Table of Contents