EasyManua.ls Logo

LSIS LSLV-S100 - Page 288

LSIS LSLV-S100
411 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
274
Table of Functions
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F SL Ref.
51
21
0h1333
Energy saving
level
Energy Save 0-30(%) 0 O/A O X p.166
60 0h133C
Acc/Dec time
transition
frequency
Xcel Change
Fr
0.00-Maximum
frequency(Hz)
0.00 X/A O I/P p.92
61 0h133D
Rotation count
speed gain
Load Spd
Gain
0.1~6000.0[%]
100.0 O/A O I/P -
62 0h133E
Rotation count
speed scale
Load Spd
Scale
0
x 1
0: x 1 O/A O I/P -
1
x 0.1
2
x 0.01
3
x 0.001
4
x 0.0001
63 0h133F
Rotation count
speed unit
Load Spd
Unit
0
Rpm
0: rpm O/A O I/P -
1
mpm
64 0h1340
Cooling fan
control
FAN Control
0
During Run
0:Durin
g Run
O/A O I/P
p.179
1
Always ON
2
Temp
Control
65 0h1341
Up/down
operation
frequency save
U/D Save
Mode
0
No
0:No O/A O I/P p.129
1 Yes
66 0h1342
Output contact
On/Off control
options
On/Off Ctrl
Src
0
None
0:None X/A O I/P p.129
1
V1
3
V2
4
I2
6
Pulse
67 0h1343
Output contact
On level
On-Ctrl Level
Output contact
off level-
100.00%
90.00 X/A O I/P p.190
68 0h1344
Output contact
Off level
Off-Ctrl Level
-100.00-output
contact on level
(%)
10.00 X/A O I/P p.190
70 0h1346
Safe operation
selection
Run En Mode
0
Always
Enable
0:Alway
s
Enable
X/A O I/P p.131
1
DI
Dependent
71
22
0h1347
Safe operation
stop options
Run Dis Stop
0
Free-Run
0:Free-
Run
X/A O I/P p.131
1
Q-Stop
2
Q-Stop
Resume
21
Displayed if Ad.50 is not set to 0 (None).
22
Displayed when Ad.70 is set to 1 (DI Dependent).

Table of Contents

Other manuals for LSIS LSLV-S100

Related product manuals