Table of Functions
281
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property
*
V/F SL Ref.
search
on
acceleratio
n
0010
When
starting on
initializatio
n
after fault
trip
0100
When
restarting
after
instantane
ous power
interruptio
n
1000
When
starting
with power
on
72
38
0h1448
Speed search
reference current
SS Sup-
Current
80-200(%) 150 O/A O I/P p.170
73
39
0h1449
Speed search
proportional gain
SS P-Gain 0-9999
Flying
Start-1
: 100
O/A O I p.170
Flying
Start-2
: 600
40
74
39
0h144A
Speed search
integral gain
SS I-Gain 0-9999
Flying
Start-1
: 200
O/A O I p.170
Flying
Start-2
: 1000
75
39
0h144B
Output blocking
time before
speed search
SS Block
Time
0.0-60.0(s) 1.0 X/A O I/P p.170
38
Displayed when any of the Cn.71 code bits are set to 1 and Cn70 is set to 0 (Flying Start-1).
39
Displayed when any of the Cn.71 code bits are set to 1.
40
The initial value is 1200 when the motor-rated capacity is less than 7.5 kW