Table of Functions
303
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property
*
V/F SL Ref.
001
0
At constant
speed
010
0
At
deceleratio
n
100
0
FluxBraking
51
0h1B33 Stall frequency1 Stall Freq 1
Start frequency-
Stall
frequency2(Hz)
60.00
O/A O X p.210
52
0h1B34 Stall level1 Stall Level 1 30-250(%) 180
X/A O X p.210
53
0h1B35 Stall frequency2 Stall Freq 2
Stall frequency1-
Stall
frequency3(Hz)
60.00
O/A O X p.210
54
0h1B36
Stall level2
Stall Level 2
30-250(%)
180
X/A O X p.210
55
0h1B37 Stall frequency3 Stall Freq 3
Stall frequency2-
Stall
frequency4(Hz)
60.00
O/A O X p.210
56
0h1B38
Stall level3
Stall Level 3
30-250(%)
180
X/A O X p.210
57
0h1B39 Stall frequency4 Stall Freq 4
Stall frequency3-
Maximum
frequency(Hz)
60.00
O/A O X
p.210
58
0h1B3A
Stall level4
Stall Level 4
30-250(%)
180
X/A O X p.210
59
0h1B3B
Flux braking
gain
Flux Brake
Kp
0 ~ 150[%] 0
O/A O I -
60
0h1B3C
CAP diagnosis
level
CAP. Diag
Perc
10 ~ 100[%] 0
O/A O I/P -
61
65
0h1B3D
CAP diagnosis
mode
C A P. D i ag
0 None
0
X/A O I/P -
1 Ref Diag
2
Pre Diag
3 Init Diag
62
65
0h1B3E
CAP Exchange
Level
CAP
Exchange
Level
50.0 ~ 95.0[%] 0
X/A O I/P -
63
65
0h1B3F CAP Diag Level
CAP Diag
Level
0.0~100.0[%] 0.0
-/A O I/P -
66
0h1B42
DB resistor
warning level
DB
Warn %ED
0-30(%) 0
O/A O I/P p.218
65
The Pr.61-63 codes are displayed when the Pr.60(CAP.DiagPrec) is set to more than 0.