304
Table of Functions
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property
*
V/F SL Ref.
73 0h1B22
Speed deviation
trip
Speed Dev
Trip
0
No
0:No O/A O I/P
1
Yes
74
66
0h1B23
Speed deviation
band
Speed Dev
Band
1 ~ 20 5 O/A O I/P
75
66
0h1B24
Speed deviation
time
Speed Dev
Time
0 ~ 120 60 O/A O I/P
79 0h1B4F
Cooling fan fault
selection
FAN Trip
Mode
0 Trip
1:Warnin
g
O/A O I/P p.221
1 Warning
80 0h1B50
Motion
selection
at option trip
Opt Trip
Mode
0 None
1:Free-
Run
O/A O I/P p.225
1 Free-Run
2
Dec
81 0h1B51
Low voltage
fault decision
delay time
LVT Delay 0.0-60.0(s) 0.0 X/A O I/P p.221
82 0h1B52 LV2 Selection LV2 Enable
0 No
0 X/A O I/P -
1
Yes
86 0h1B56
Accumulated
percent of fan
usage
Fan Time
Perc
0.0~100.0[%] 0.0 -/A O I/P -
87 0h1B57
Fan exchange
warning level
Fan
Exchange
level
0.0~100.0[%] 90.0 O/A O I/P -
88
67
0h1B58 Fan reset time Fan Time Rst
0 No
0 X/A O I/P -
1
Yes
89 0h1B59 CAP, FAN Status
C A P, FA N
State
Bit
00~10
0 -/A O I/P -
00
-
01
CAP
Warning
10
FAN
Warning
90
67
0h1B5A
Warning
information
- - - -/7 O I/P -
91
67
0h1B5B Fault history 1 - - - -/7 O I/P -
92
67
0h1B5C Fault history 2 - - - -/7 O I/P -
66
Displayed when Pr.73 is set to 1(YES)
67
Will not be displayed when an LCD keypad is in use.