MANUAL NUMBER 160339
REVISION 09SEPT04 PAGE 17
TROUBLE SHOOTING GUIDE
SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
All Protection Panel lamps off. No power to system
Check connections to &
voltage of vehicle batteries.
Check system fuse (15A).
Below 9 volts the system will
not function
Protection Panel green
“SYSTEM OK” lamp blinking.
Low battery voltage
Check connections to &
voltage of vehicle batteries.
Below 22 volts the system will
provide low voltage indication.
Protection Panel green
“SYSTEM OK” lamp off,
yellow fire “TROUBLE” lamp
on, red fire “ALARM” lamp on
solid and audible alarm on.
System automatically
discharged
Correct the cause of the fire
and reset the system as
described in the system reset
portion of this manual
Protection Panel green
“SYSTEM OK” lamp off,
yellow fire “TROUBLE” lamp
on, red fire “ALARM” lamp on
blinking and audible alarm on.
System manually discharged
Correct the cause of the fire
and reset the system as
described in the system reset
portion of this manual
Protection Panel green
“SYSTEM OK” lamp off,
yellow fire “TROUBLE” lamp
on solid and audible alarm
beeping.
Component not connected or
damaged harness in the
extinguisher circuit
Check harness connections at
extinguisher
Check electrical
interconnections (Figure 10)
Protection Panel green
“SYSTEM OK” lamp off,
yellow fire “TROUBLE” lamp
on blinking and audible alarm
beeping.
Component not connected or
damaged harness in the fire
detection circuit
Check harness connections at
fire sensors
Check connection at EOL
Check electrical
interconnections (Figure 10)