Log-on Errors Chapter 4
WinLink™ 1000 User Manual Release 1.9 4-6
6. If your User Type is not Operator, then choose it now.
7. Enter the password.
8. If you are a user with Read-Write permission, click Options to enter the
Community options if required
9. For initial log on:
• Leave the default Community passwords,
netman
for read-write,
and
public
for read-only.
• If Community values were previously defined, enter them under
Community in the Read-Only or Read-Write boxes.
• If you are a user with read-only permission, click the Read Only
Mode check box.
The RADWIN Manager main window is displayed (see Figure 4-8).
Log-on Errors
Unsupported Device
Attempting to connect to an unsupported device on an otherwise valid IP
address (for example, a LAN printer) will result in the following error mes-
sage:
Warning
• If you log on using Local Connection, but your physical connection
is not local (i.e. anything other than a direct connection between the
managing computer and the IDU), then any configuration you carry
out may affect other links in the network. You will not be able to do
this!
• Network log on (IP address to the ODU) is recommended.
• If you log on via an over-the-air IP address, you will receive a warn-
ing. If you reset the site to which you are connected to factory set-
tings, you can lock yourself out of the link.
Note
• If you log on using Local Connection through a PoE device, you will
need to connect it to the managing computer using a crossed Ether-
net cable.
• The default IP address for the ODU is 10.0.0.120. The subnet mask is
255.0.0.0.
• The actual IP address is defined during link configuration (see Site
Management: IP Address and VLAN on page 8-7. See also,
Appendix D).