Explanation of Chronological Sequence
"RF removed"; start "Best possible standstill"
with removal of RF signal at X1 the recommended o sequence
starts and "best possible standstill" (see rmware function
description).
"Brake contact actuated":
Brake contact in DKC**.3 actuated at X6,
Brake contact parameterizable as N/C or N/O contact (see rmware
functional description)
"Brake closed":
brake connected via brake contact is closed.
"Contactor K1 removed"; "Mains contactor at X5 removed":
start DC bus dynamic brake discharge
"U
D
-Signal":
Signal output at X3
(not for DKC**.3-016)
"Control voltage removed"
DC24V supply at X1
"Bb contact open":
without DC24V
at X1 the Bb relay in DKC**.3 is brought into home
position (N/O opened).
Note: Removing the DC24V at X1 causes the Bb contact to open,
the removal of the U
D
signal and the loss of the diagnosis
displayed at H1 despite the existing DC bus voltage.
customerservice@hyperdynesystems.com | (479) 422-0390

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rexroth Indramat ECODRIVE03 Series and is the answer not in the manual?

Rexroth Indramat ECODRIVE03 Series Specifications

General IconGeneral
BrandRexroth Indramat
ModelECODRIVE03 Series
CategoryController
LanguageEnglish

Related product manuals