7. Take the new optics cover out of the packaging and remove the protective cap for
t
he seal.
8. If necessary, remove any remnants of packaging.
9.
Place the optics cover on the safety laser scanner and fit the new fixing screws 1
to 3.
10. When fitting the new optics cover, ensure the arrow on the top of the cover points
to the front and that the optics cover is fully in contact without a gap.
11. Tighten the screws using the set tightening torque.
12. Make sure that the optics cover is clear of dirt and damage.
Recommissioning the safety laser scanner:
b
Correctly re-mount the safety laser scanner.
b
Connect the system plug of the safety laser scanner.
After power up, the safety laser scanner automatically reads the saved configura‐
tion from the system plug.
b
Now perform an optics cover calibration using the CDS.
Further topics
"A
ccessories", page 138
"Additional accessories", page 140
"Mounting", page 58
"Recommissioning", page 105
9.5 Replacing the device
Overview
T
he device has a configuration memory in the system plug. In case of device replace‐
ment, the existing configuration is automatically transferred to the newly connected
device.
Approach
1. Remove the system plug.
2. Remove the safety laser scanner.
3. Correctly mount the new safety laser scanner.
4. Connect the system plug of the safety laser scanner.
After power up, the safety laser scanner automatically reads the saved configura‐
tion from the system plug.
5. Carry out the check as per the requirements for daily checking.
Compatibility mode
If a ne
w device is connected to an older system plug, the new device will operate auto‐
matically in compatibility mode.
Reasons for activating the compatibility mode
System plug serial number < 12210000
System plug in which the following configuration is saved:
°
A configuration that only supports the compatibility mode.
°
A configuration that has been configured in the compatibility mode.
°
A configuration that has been configured with a CDS version < 3.6.7.
NOTE
If com
patibility cannot be established, e.g., if an S300 Professional is replaced with an
S300 Advanced, the device switches to the “Waiting for configuration” state. In this
case the 7-segment display indicates .
MAINTENANCE 9
8010948/ZA21/2020-06-18 | SICK O P E R A T I N G I N S T R U C T I O N S | S300
111
Subject to change without notice

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK S300 Series and is the answer not in the manual?

SICK S300 Series Specifications

General IconGeneral
Scanning angle270 °
Number of monitoring cases4
Protection classIP65
Number of scanning planes1
Angular resolution0.5°
InterfaceRS-422, Ethernet
Supply voltage24 V DC
Ambient operating temperature0 °C ... +50 °C
Laser class1 (IEC 60825-1)
Storage temperature–25 °C ... +70 °C
Protective field range0.1 m to 3 m