Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
215
Relay duration (2.10.2.4.)
Adjusts the minimum contact closure duration of a relay set as a flow sampler [Relay
Function (2.8.1.4.) (Page 195) = Flow Sampler], if desired.
Index
Global
Values
Range: 0.1 ... 1024
Preset: 0.2 seconds
Related
Relay function (2.8.1.4.) (Page 195)
Enter minimum contact closure duration (in seconds) required by the device connected.
Relay duration (2.10.1.3.) ON time
Relay duration (2.10.1.3.) OFF time
Relay selector (2.10.2.5.)
Sets the relay index for all parameters applicable to this sub-menu.
Relay interval setpoint (2.10.2.6.)
Sets the length of time between starts, in hours.
Index
Relay
Values
Range: 0 ... 9000 hours
Preset: 0.000 hours
Altered by
Preset applications (2.8.1.3.) (Page 194)
Related
Relay function (2.8.1.4.) (Page 195)