Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
217
Flush cycles (2.10.3.3.)
Sets the number of pump cycles requiring flush control.
Index
Single-point model
Dual-point model
Global
Relay
Values
Range: 0 ... 34464
Preset: 0
Related
Relay Function (2.8.1.4.) (Page 195) = Flush Valve
If three flush cycles are required after every ten pump cycles, then:
Flush Interval (2.10.3.4.) (Page 217) =
10
Flush Cycles (2.10.3.3.) =
3
Flush interval (2.10.3.4.)
Sets the number of pump cycles before flush control is enabled.
Index
Single-point model
Dual-point model
Global
Relay
Values
Range: 0 ... 37856
Preset: 0
Related
Relay Function (2.8.1.4.) (Page 195) = Flush Valve
To start a new flush cycle every ten times the pumps are run, set this to
10
.
Flush duration (2.10.3.5.)
Sets the length of time for each flush cycle that the flush control is active.
Index
Single-point model
Dual-point model
Global
Relay
Values
Range: 0.000 ... 9999 seconds
Preset: 0.000 seconds
Related
Relay Function (2.8.1.4.) (Page 195) = Flush Valve