Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
229
Display after Auto False Echo Suppression
TVT curve (learned)
Material le
vel
False echo
Hover level (2.11.3.4.)
Defines (in percent) how high the TVT curve is placed above the profile, relative to the
largest echo. When the device is located in the center of the vessel, lower this parameter to
prevent multiple echo detections.
Values
Range: 0 ... 100%
Preset: 33 %
Shaper mode (2.11.3.5.)
Turns the TVT Shaper ON or OFF.
Index
Single-point model
Dual-point model
Global
Transducer
Options
*OFF
ON
Related
TVT Shaper (2.11.4.) (Page 231)
Turn the TVT Shaper ON before using TVT Shaper (2.11.4) (Page 231) and afterwards. Turn
the TVT Shaper ON and OFF while monitoring the effect to pick up the true echo.