Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
230 Operating Instructions, 06/2018, A5E36281317-AC
Selects the TVT Curve used.
*Short Curved
Material (2.1.6.) (Page 165)
• Long confidence (3.2.11.2.) (Page 262)
• TVT slope minimum (2.11.3.9.) (Page 231)
Select the TVT type which gives the highest Long Confidence (3.2.11.2.) (Page 262) under
all level conditions. Use this parameter with caution, and do not use TVT
with the
or
Algorithm (2.11.2.2.) (Page 222).
Adjusts the TVT Curve height to ignore false echoes (or pick up true echoes) near the start
of the Echo Profile.
• Blanking (2.2.6.) (Page 171)
• TVT ms (2.11.3.8) (Page 231)
Enter the minimum TVT Curve start point (in dB above 1 μV RMS).
This feature should only be used if increased Blanking (2.2.6.) (Page 171) would extend into
the measurement range farther than desired.