EasyManua.ls Logo

Siemens HydroRanger 200 HMI - Page 287

Siemens HydroRanger 200 HMI
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnosing and troubleshooting
10.3 Common problems chart
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
285
Symptom
Possible cause
Action
Incorrect vessel or PMD
dimensions
For volume application: Verify vessel dimensions.
See Vessel shape (2.7.2.) (Page 186).
For flow application: Verify PMD dimensions. See
PMD dimensions (2.13.5.) (Page 246).
Symptom
cause
Action
Relay not activating
Relay not programmed
Program relay.
Incorrect relay setpoints
Verify setpoints.
Relay not activating
correctly
Incorrect relay setpoints Verify setpoints.
Configuration error 130
displayed
Relay/pump configuration
errors - possible causes
include:
A relay is assigned to
more than one function
(e.g. Relay 2 is as-
signed to both an ex-
ternal totalizer and a
pump).
Pump setpoints are out
of order.
Wall cling adjustment
range is too large.
Verify that each relay is assigned to one
function only. Review relay assignments
under Relay selector (2.8.1.1.) (Page 193)
and Other Control (2.10.) (Page 210).
Verify that all 'ON' setpoints are greater
than their respective 'OFF' setpoints for
pump down applications (or vice versa for
pump up applications).
Ensure range set in Level setpoint varia-
tion (2.8.2.6.2.) (Page 204) has not caused
'ON' or 'OFF' setpoints to overlap.
Echo profile request
results in an error icon
that displays for 5 sec-
onds before returning to
the echo profile request
menu.
Another external commu-
nication is trying to access
an echo profile at the
same time.
Wait for several seconds and then retry the
echo profile request, or disconnect / disable
any external communications that may be
requesting an echo profile.
Display blank, trans-
ducer not pulsing.
No power. Check power supply, wiring, or power fuse.
No response to pro-
grammer.
Obstructed infrared inter-
face, defective program-
mer.
Check programmer usage: 15 cm (6 inch)
from faceplate pointed at upper target.
Displays Short and
tb:(#).
Short circuited transducer
cable, or defective trans-
ducer at indicated terminal
block number.
Repair or replace as necessary.
Displays Open and
tb:(#).
Transducer not connected
or connection reversed.
Check connection to displayed terminal
blocks.
Open circuited transducer
cable, or defective trans-
ducer at indicated terminal
block number.
Repair or replace as necessary.
Displays LOE. Weak or non-existent
echo.
Relocate and/or re-aim transducer at material.
Proceed toMeasurement difficulties
(Page 289).

Table of Contents

Related product manuals