Diagnosing and troubleshooting
10.3 Common problems chart
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
285
Incorrect vessel or PMD
dimensions
For volume application: Verify vessel dimensions.
See Vessel shape (2.7.2.) (Page 186).
For flow application: Verify PMD dimensions. See
PMD dimensions (2.13.5.) (Page 246).
Relay not activating
Incorrect relay setpoints
Relay not activating
Incorrect relay setpoints Verify setpoints.
Configuration error 130
displayed
Relay/pump configuration
errors - possible causes
include:
• A relay is assigned to
more than one function
(e.g. Relay 2 is as-
signed to both an ex-
ternal totalizer and a
pump).
• Pump setpoints are out
of order.
• Wall cling adjustment
range is too large.
• Verify that each relay is assigned to one
function only. Review relay assignments
under Relay selector (2.8.1.1.) (Page 193)
and Other Control (2.10.) (Page 210).
• Verify that all 'ON' setpoints are greater
than their respective 'OFF' setpoints for
pump down applications (or vice versa for
pump up applications).
• Ensure range set in Level setpoint varia-
tion (2.8.2.6.2.) (Page 204) has not caused
'ON' or 'OFF' setpoints to overlap.
Echo profile request
results in an error icon
that displays for 5 sec-
onds before returning to
the echo profile request
Another external commu-
nication is trying to access
an echo profile at the
same time.
Wait for several seconds and then retry the
echo profile request, or disconnect / disable
any external communications that may be
requesting an echo profile.
Display blank, trans-
No power. Check power supply, wiring, or power fuse.
No response to pro-
grammer.
Obstructed infrared inter-
face, defective program-
Check programmer usage: 15 cm (6 inch)
from faceplate pointed at upper target.
Displays Short and
tb:(#).
Short circuited transducer
cable, or defective trans-
ducer at indicated terminal
Repair or replace as necessary.
Displays Open and
tb:(#).
Transducer not connected
Check connection to displayed terminal
Open circuited transducer
cable, or defective trans-
ducer at indicated terminal
Repair or replace as necessary.
Displays LOE. Weak or non-existent
echo.
Relocate and/or re-aim transducer at material.
Proceed toMeasurement difficulties