5.2 Diagnostics via STARTER
Function Manual
104 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Example of a measurement
Assumption:
The actual speed (r0063) is to be output for a drive via measuring socket T1.
How do you do it?
1. Connect and set the measuring device.
2. Interconnect the signal (e.g. STARTER).
Interconnect the connector input (CI) belonging to the measuring socket with the desired
connector output (CO).
CI: p0771[1] = CO: r0063
3. Parameterize the signal characteristic (scaling, offset, limitation).
Function diagrams (see SINAMICS S110 List Manual)
8134 measuring sockets
Overview of important parameters (see SINAMICS S110 List Manual)
Adjustable parameters
p0771[0...1] CI: Measuring sockets signal source
p0777[0...1] Measuring sockets characteristic value x1
P0778[0...1] Measuring sockets characteristic value y1
p0779[0...1] Measuring sockets characteristic value x2
p0780[0...1] Measuring sockets characteristic value y2
p0783[0...1] Measuring sockets offset
p0784[0...1] Measuring sockets limit on/off
Display parameters
r0772[0...1] Measuring sockets output signal
r0774[0...1] Measuring sockets output voltage
r0786[0...1] Measuring sockets normalization per volt