EasyManua.ls Logo

Siemens SINAMICS S110 - Page 105

Siemens SINAMICS S110
714 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnostics
5.2 Diagnostics via STARTER
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
103
Which signal can be output via measuring sockets?
The signal to be output via a measuring socket is specified by parameterizing the connector
input p0771[0...1].
Important measuring signals (examples):
r0060 CO: Speed setpoint before speed setpoint filter
r0063 CO: Actual speed value
r0069[0...2] CO: Phase currents actual value
r0075 CO: Field-generating current setpoint
r0076 CO: Field-generating actual current
r0077 CO: Torque-generating current setpoint
r0078 CO: Torque-generating actual current
Scaling
Scaling specifies how the measuring signal is processed. A straight line with 2 points must
be defined for this purpose.
Example:
x1 / y1 = 0.0% / 2.49 V x2 / y2 = 100.0% / 4.98 V (default setting)
– 0.0% is mapped onto 2.49 V
– 100.0% is mapped onto 0.00 V
Offset
The offset is applied additively to the signal to be output. The signal to be output can thus be
displayed within the measuring range.
Limitation
Limitation On
If signals are output outside the permissible measuring range, the signal is limited to 4.98
V or to 0V.
Limitation off
The output of signals outside the permissible measuring range causes a signal overflow.
In the event of an overflow, the signal jumps from 0 V to 4.98 V or from 4.98 to 0 V.

Table of Contents

Other manuals for Siemens SINAMICS S110

Related product manuals