EasyManua.ls Logo

Siemens SINAMICS S110 - Page 502

Siemens SINAMICS S110
714 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety Integrated Functions
8.9 Acceptance test and acceptance report
Function Manual
500 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Trace evaluation:
SLS function with SLS level 1 is active (see bits "deselection SLS", "selection SLS bit 0",
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level
bit 1")
Drive is accelerated beyond the SLS limit (time axis from approx. -400 ms)
Exceeding of the limit is recognized (time axis 0 ms)
Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
Fault response STOP C is initiated (see bit "STOP C active" and "SS2 active")
Drive is decelerated to a standstill (see curve of Drive_1.r9714[0])
After the SS2 timer has expired the follow-up function SOS is activated (time axis 500
ms)
The "SOS active" bit is set and "SLS active" is reset
Note
Small time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.

Table of Contents

Other manuals for Siemens SINAMICS S110

Related product manuals