Safety Integrated Functions
8.9 Acceptance test and acceptance report
Function Manual
516 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
%LWWUDFNV
'ULYHBU>@6,0RWLRQGLDJQRVWLFVVSHHGDFWXDOORDGVLGHVSHHGYDOXHRQ&RQWURO8QLW
6723$RU%DFWLYH
6HOHFW6/6ELW
6HOHFW6/6ELW
'HVHOHFW6/6
,QWHUQDOHYHQW
6/6DFWLYH
672DFWLYH
$FWLYH6/6OHYHOELW
$FWLYH6/6OHYHOELW
Figure 8-49 Example trace SLS without encoder with STOP A
Trace evaluation:
SLS function with SLS level 1 is active (see bits "deselection SLS", "selection SLS bit 0",
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level
bit 1")
Drive is accelerated beyond the SLS limit (time axis from approx. -800 ms)
Exceeding of the limit is recognized (time axis 0 ms)
Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
Fault response STOP A is initiated (time axis 0 ms; see bit "STOP A or B active" and
"STO active")
Drive coasts (see red curve of r9714[0])
Note
Small time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.