Communication
9.2 Communication according to PROFIdrive
Function Manual
534 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Bit Meaning Remarks Parameter
0 Inhibit ramp-function generator
Set ramp-function generator output to zero
1 Restart ramp-function generator Restart ramp-function generator
0 Freeze ramp-function generator
BI: p1141 5
Note:
The ramp-function generator cannot be frozen via p1141 in jog mode (r0046.31 = 1).
1 Enable setpoint 6 Enable speed setpoint
0 Inhibit setpoint
Set ramp-function generator input to zero
BI: p1142
0/1 Acknowledge fault Acknowledge fault
0 No effect
BI: p2103 7
Note:
Faults are acknowledged at a 0/1 edge via BI: p2103.
8..9 Reserved - - -
1 Master control by PLC
This signal must be set so that the process data
transferred via PROFIdrive are accepted and
become effective.
Master control by PLC
0 PLC has no master control
Process data transferred via PROFIdrive are
rejected - i.e. assumed to be zero.
BI: p0854 10
Note:
This bit should not be set to "1" until the PROFIdrive has returned an appropriate status via ZSW1.9 = "1".
1 Setpoint inversion 11 Setpoint inversion
(Only with "extended setpoint channel"
and "extended ramp-function
generator")
0 No setpoint inversion
BI: p1113
12 Reserved - - -
1 Motorized potentiometer, setpoint, raise 13 Motorized potentiometer, setpoint, raise
(Only with "extended setpoint channel"
and "extended ramp-function
generator")
0 Motorized potentiometer setpoint raise not
selected
BI: p1035
1 Motorized potentiometer, setpoint, lower 14 Motorized potentiometer, setpoint, lower
(Only with "extended setpoint channel"
and "extended ramp-function
generator")
0 Motorized potentiometer setpoint lower not
selected
BI: p1036
15 Reserved - - -