Communication
9.2 Communication according to PROFIdrive
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
553
Bit Meaning Remarks Parameter
1 No thermal overload in power unit alarm
The temperature of the heat sink in the power unit is
within the permissible range.
7 No thermal overload in power unit
alarm
0 Thermal overload in power unit alarm
The temperature of the heat sink in the power unit is
outside the permissible range.
If the overtemperature remains, the drive switches
itself off after approx. 20 s.
BO: r2135.15
1 The speed setpoint/actual value is within the
tolerance p2163: The signal is switched on after the
delay specified in p2167 has elapsed.
8 Speed setp - act val deviation in
tolerance t_on
0 The speed setpoint/actual value is outside the
tolerance.
BO: r2199.4
9,10 Reserved - - -
11 Controller enable 1 Controller enable BO: r0899.8
12 Drive ready 1 Drive ready BO: r0899.7
1 Pulses enabled
The pulses for activating the motor are enabled.
Pulses enabled
0 Pulses inhibited
BO: r0899.11 13
Application:
Armature short-circuit protection must only be switched on when the pulses are inhibited.
This signal can be evaluated as one of many conditions when armature short-circuit protection is activated.
14,15 Reserved - - -
AKTSATZ
See function diagram [3650].
Table 9- 19 Description of AKTSATZ (active traversing block/MDI active)
Bit Meaning Remarks Parameter
0 Active traversing block, bit 0 – BO: r2670.0
1 Active traversing block, bit 1 – BO: r2670.1
2 Active traversing block, bit 2 – BO: r2670.2
3 Active traversing block, bit 3 – BO: r2670.3
4 Active traversing block, bit 4 – BO: r2670.4
5 Active traversing block, bit 5 –
Active traversing block (6-bit counter)
BO: r2670.5
6 ... 14 Reserved – – –
1 MDI active 15 MDI active
0 MDI not active
BO: r2670.15