Basic information about the drive system
10.1 Parameter
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
657
Resetting parameters
The parameters can be reset to the factory setting as follows:
Reset parameters - current drive object
p0970 = 1; automatically reset to 0
Reset parameters - all parameters drive object "Control Unit"
p0009 = 30 parameter reset
p0976 = 1; automatically reset to 0
Access level
The parameters are subdivided into access levels. The SINAMICS S110 List Manual
specifies the access level at which the parameter can be displayed and modified. The
required access levels 0 to 4 can be set in p0003.
Table 10- 1 Access levels
Access level Remark
0 User-defined Parameter from the user-defined list
1 Standard Parameters for the simplest operator functions (e.g. p1120 = ramp-function
generator ramp-up time).
2 Extended Parameters to handle the basic functions of the device.
3 Expert Expert knowledge is already required for this parameter (e.g. knowledge
about BICO parameterization).
4 Service Please contact your local Siemens office for the password for parameters
with access level 4 (Service). It must be entered into p3950.
Note
Parameter p0003 is only available on the drive object Control Unit.